1000 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 11.58V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 76.43V (18.42%)
Voltage at Load403.4 VLine Loss: 20062.5 W
Max Power & Breaker718.8 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12355.3 V (2977.18%)0.0 V20380.46 V (4910.96%)21400000.0 WDrop High
2.5 mm²24 A18 A7413.18 V (1786.31%)0.0 V12228.28 V (2946.57%)12840000.0 WDrop High
4 mm²32 A25 A4633.24 V (1116.44%)0.0 V7642.67 V (1841.61%)8025000.0 WDrop High
6 mm²41 A32 A3088.82 V (744.29%)0.0 V5095.12 V (1227.74%)5350000.0 WDrop High
10 mm²57 A44 A1853.29 V (446.58%)0.0 V3057.07 V (736.64%)3210000.0 WDrop High
16 mm²76 A59 A1158.31 V (279.11%)0.0 V1910.67 V (460.4%)2006250.0 WDrop High
25 mm²101 A78 A741.32 V (178.63%)0.0 V1222.83 V (294.66%)1284000.0 WDrop High
35 mm²125 A97 A529.51 V (127.59%)0.0 V873.45 V (210.47%)917142.9 WDrop High
50 mm²151 A118 A370.66 V (89.32%)44.3 V611.41 V (147.33%)642000.0 WDrop High
70 mm²192 A150 A264.76 V (63.8%)150.2 V436.72 V (105.23%)458571.4 WDrop High
95 mm²232 A181 A195.08 V (47.01%)219.9 V321.8 V (77.54%)337894.7 WDrop High
120 mm²269 A210 A154.44 V (37.21%)260.6 V254.76 V (61.39%)267500.0 WDrop High
150 mm²309 A241 A123.55 V (29.77%)291.4 V203.8 V (49.11%)214000.0 WDrop High
185 mm²353 A275 A100.18 V (24.14%)314.8 V165.25 V (39.82%)173513.5 WDrop High
240 mm²415 A324 A77.22 V (18.61%)337.8 V127.38 V (30.69%)133750.0 WDrop High
300 mm²477 A372 A61.78 V (14.89%)353.2 V101.9 V (24.55%)107000.0 WDrop High
400 mm²570 A445 A46.33 V (11.16%)368.7 V76.43 V (18.42%)80250.0 WDrop High

FAQ — 1000 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 1000A at 500 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 1000A over 500m at 415V (voltage drop: 11.58V or 2.79%).

What is the power capacity of 1000A at 415V?

At unity power factor, 1000A at 415V supports 718.8 kW with a standard 1000A circuit breaker.