1000 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.08V (0.5%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.88V (1.66%)
Voltage at Load412.9 VLine Loss: 3611.2 W
Max Power & Breaker718.8 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (267.95%)0.0 V1834.24 V (441.99%)1926000.0 WDrop High
2.5 mm²24 A18 A667.19 V (160.77%)0.0 V1100.55 V (265.19%)1155600.0 WDrop High
4 mm²32 A25 A416.99 V (100.48%)0.0 V687.84 V (165.74%)722250.0 WDrop High
6 mm²41 A32 A277.99 V (66.99%)137.0 V458.56 V (110.5%)481500.0 WDrop High
10 mm²57 A44 A166.8 V (40.19%)248.2 V275.14 V (66.3%)288900.0 WDrop High
16 mm²76 A59 A104.25 V (25.12%)310.8 V171.96 V (41.44%)180562.5 WDrop High
25 mm²101 A78 A66.72 V (16.08%)348.3 V110.05 V (26.52%)115560.0 WDrop High
35 mm²125 A97 A47.66 V (11.48%)367.3 V78.61 V (18.94%)82542.9 WDrop High
50 mm²151 A118 A33.36 V (8.04%)381.6 V55.03 V (13.26%)57780.0 WDrop High
70 mm²192 A150 A23.83 V (5.74%)391.2 V39.31 V (9.47%)41271.4 WDrop High
95 mm²232 A181 A17.56 V (4.23%)397.4 V28.96 V (6.98%)30410.5 WDrop High
120 mm²269 A210 A13.9 V (3.35%)401.1 V22.93 V (5.52%)24075.0 WDrop High
150 mm²309 A241 A11.12 V (2.68%)403.9 V18.34 V (4.42%)19260.0 WDrop High
185 mm²353 A275 A9.02 V (2.17%)406.0 V14.87 V (3.58%)15616.2 WDrop High
240 mm²415 A324 A6.95 V (1.67%)408.1 V11.46 V (2.76%)12037.5 WDrop High
300 mm²477 A372 A5.56 V (1.34%)409.4 V9.17 V (2.21%)9630.0 WDrop High
400 mm²570 A445 A4.17 V (1.0%)410.8 V6.88 V (1.66%)7222.5 WDrop High

FAQ — 1000 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 1000A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 45m at 415V (voltage drop: 2.08V or 0.5%).

What is the power capacity of 1000A at 415V?

At unity power factor, 1000A at 415V supports 718.8 kW with a standard 1000A circuit breaker.