20 Amp Cable Size at 70 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 12.97V (1.88%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 14.27V (2.07%)
Voltage at Load677.0 VLine Loss: 449.4 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.59 V (5.01%)655.4 V57.07 V (8.27%)1198.4 WDrop High
2.5 mm²24 A18 A20.76 V (3.01%)669.2 V34.24 V (4.96%)719.0 W~ ≤5%
4 mm²32 A25 A12.97 V (1.88%)677.0 V21.4 V (3.1%)449.4 W✓ OK (≤3%)
6 mm²41 A32 A8.65 V (1.25%)681.4 V14.27 V (2.07%)299.6 W✓ OK (≤3%)
10 mm²57 A44 A5.19 V (0.75%)684.8 V8.56 V (1.24%)179.8 W✓ OK (≤3%)
16 mm²76 A59 A3.24 V (0.47%)686.8 V5.35 V (0.78%)112.3 W✓ OK (≤3%)
25 mm²101 A78 A2.08 V (0.3%)687.9 V3.42 V (0.5%)71.9 W✓ OK (≤3%)
35 mm²125 A97 A1.48 V (0.21%)688.5 V2.45 V (0.35%)51.4 W✓ OK (≤3%)
50 mm²151 A118 A1.04 V (0.15%)689.0 V1.71 V (0.25%)36.0 W✓ OK (≤3%)
70 mm²192 A150 A0.74 V (0.11%)689.3 V1.22 V (0.18%)25.7 W✓ OK (≤3%)
95 mm²232 A181 A0.55 V (0.08%)689.5 V0.9 V (0.13%)18.9 W✓ OK (≤3%)
120 mm²269 A210 A0.43 V (0.06%)689.6 V0.71 V (0.1%)15.0 W✓ OK (≤3%)
150 mm²309 A241 A0.35 V (0.05%)689.7 V0.57 V (0.08%)12.0 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.04%)689.7 V0.46 V (0.07%)9.7 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.03%)689.8 V0.36 V (0.05%)7.5 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.03%)689.8 V0.29 V (0.04%)6.0 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.02%)689.9 V0.21 V (0.03%)4.5 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 70 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 70 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 20A over 70m at 690V (voltage drop: 12.97V or 1.88%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.