110 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 5.95V (2.59%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 6.21V (2.7%)
Voltage at Load224.1 VLine Loss: 654.2 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A376.64 V (163.76%)0.0 V621.28 V (270.12%)41430.4 WDrop High
2.5 mm²24 A18 A225.98 V (98.25%)4.0 V372.77 V (162.07%)24858.2 WDrop High
4 mm²32 A25 A141.24 V (61.41%)88.8 V232.98 V (101.3%)15536.4 WDrop High
6 mm²41 A32 A94.16 V (40.94%)135.8 V155.32 V (67.53%)10357.6 WDrop High
10 mm²57 A44 A56.5 V (24.56%)173.5 V93.19 V (40.52%)6214.6 WDrop High
16 mm²76 A59 A35.31 V (15.35%)194.7 V58.24 V (25.32%)3884.1 WDrop High
25 mm²101 A78 A22.6 V (9.83%)207.4 V37.28 V (16.21%)2485.8 WDrop High
35 mm²125 A97 A16.14 V (7.02%)213.9 V26.63 V (11.58%)1775.6 WDrop High
50 mm²151 A118 A11.3 V (4.91%)218.7 V18.64 V (8.1%)1242.9 W~ ≤5%
70 mm²192 A150 A8.07 V (3.51%)221.9 V13.31 V (5.79%)887.8 W~ ≤5%
95 mm²232 A181 A5.95 V (2.59%)224.1 V9.81 V (4.27%)654.2 W✓ OK (≤3%)
120 mm²269 A210 A4.71 V (2.05%)225.3 V7.77 V (3.38%)517.9 W✓ OK (≤3%)
150 mm²309 A241 A3.77 V (1.64%)226.2 V6.21 V (2.7%)414.3 W✓ OK (≤3%)
185 mm²353 A275 A3.05 V (1.33%)226.9 V5.04 V (2.19%)335.9 W✓ OK (≤3%)
240 mm²415 A324 A2.35 V (1.02%)227.6 V3.88 V (1.69%)258.9 W✓ OK (≤3%)
300 mm²477 A372 A1.88 V (0.82%)228.1 V3.11 V (1.35%)207.2 W✓ OK (≤3%)
400 mm²570 A445 A1.41 V (0.61%)228.6 V2.33 V (1.01%)155.4 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 110A at 120 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 110A over 120m at 230V (voltage drop: 5.95V or 2.59%).

What is the power capacity of 110A at 230V?

At unity power factor, 110A at 230V supports 25.3 kW with a standard 110A circuit breaker.