110 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 9.79V (2.36%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 11.53V (2.78%)
Voltage at Load405.2 VLine Loss: 1864.4 W
Max Power & Breaker79.07 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A326.18 V (78.6%)88.8 V538.04 V (129.65%)62145.6 WDrop High
2.5 mm²24 A18 A195.71 V (47.16%)219.3 V322.83 V (77.79%)37287.4 WDrop High
4 mm²32 A25 A122.32 V (29.47%)292.7 V201.77 V (48.62%)23304.6 WDrop High
6 mm²41 A32 A81.54 V (19.65%)333.5 V134.51 V (32.41%)15536.4 WDrop High
10 mm²57 A44 A48.93 V (11.79%)366.1 V80.71 V (19.45%)9321.8 WDrop High
16 mm²76 A59 A30.58 V (7.37%)384.4 V50.44 V (12.15%)5826.2 WDrop High
25 mm²101 A78 A19.57 V (4.72%)395.4 V32.28 V (7.78%)3728.7 WDrop High
35 mm²125 A97 A13.98 V (3.37%)401.0 V23.06 V (5.56%)2663.4 W~ ≤5%
50 mm²151 A118 A9.79 V (2.36%)405.2 V16.14 V (3.89%)1864.4 W✓ OK (≤3%)
70 mm²192 A150 A6.99 V (1.68%)408.0 V11.53 V (2.78%)1331.7 W✓ OK (≤3%)
95 mm²232 A181 A5.15 V (1.24%)409.8 V8.5 V (2.05%)981.2 W✓ OK (≤3%)
120 mm²269 A210 A4.08 V (0.98%)410.9 V6.73 V (1.62%)776.8 W✓ OK (≤3%)
150 mm²309 A241 A3.26 V (0.79%)411.7 V5.38 V (1.3%)621.5 W✓ OK (≤3%)
185 mm²353 A275 A2.64 V (0.64%)412.4 V4.36 V (1.05%)503.9 W✓ OK (≤3%)
240 mm²415 A324 A2.04 V (0.49%)413.0 V3.36 V (0.81%)388.4 W✓ OK (≤3%)
300 mm²477 A372 A1.63 V (0.39%)413.4 V2.69 V (0.65%)310.7 W✓ OK (≤3%)
400 mm²570 A445 A1.22 V (0.29%)413.8 V2.02 V (0.49%)233.0 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 110A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 110A over 120m at 415V (voltage drop: 9.79V or 2.36%).

What is the power capacity of 110A at 415V?

At unity power factor, 110A at 415V supports 79.07 kW with a standard 110A circuit breaker.