110 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 1.41V (2.94%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.33V (4.85%)
Voltage at Load46.6 VLine Loss: 155.4 W
Max Power & Breaker5.28 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A376.64 V (784.67%)0.0 V621.28 V (1294.33%)41430.4 WDrop High
2.5 mm²24 A18 A225.98 V (470.8%)0.0 V372.77 V (776.6%)24858.2 WDrop High
4 mm²32 A25 A141.24 V (294.25%)0.0 V232.98 V (485.38%)15536.4 WDrop High
6 mm²41 A32 A94.16 V (196.17%)0.0 V155.32 V (323.58%)10357.6 WDrop High
10 mm²57 A44 A56.5 V (117.7%)0.0 V93.19 V (194.15%)6214.6 WDrop High
16 mm²76 A59 A35.31 V (73.56%)12.7 V58.24 V (121.34%)3884.1 WDrop High
25 mm²101 A78 A22.6 V (47.08%)25.4 V37.28 V (77.66%)2485.8 WDrop High
35 mm²125 A97 A16.14 V (33.63%)31.9 V26.63 V (55.47%)1775.6 WDrop High
50 mm²151 A118 A11.3 V (23.54%)36.7 V18.64 V (38.83%)1242.9 WDrop High
70 mm²192 A150 A8.07 V (16.81%)39.9 V13.31 V (27.74%)887.8 WDrop High
95 mm²232 A181 A5.95 V (12.39%)42.1 V9.81 V (20.44%)654.2 WDrop High
120 mm²269 A210 A4.71 V (9.81%)43.3 V7.77 V (16.18%)517.9 WDrop High
150 mm²309 A241 A3.77 V (7.85%)44.2 V6.21 V (12.94%)414.3 WDrop High
185 mm²353 A275 A3.05 V (6.36%)44.9 V5.04 V (10.49%)335.9 WDrop High
240 mm²415 A324 A2.35 V (4.9%)45.6 V3.88 V (8.09%)258.9 W~ ≤5%
300 mm²477 A372 A1.88 V (3.92%)46.1 V3.11 V (6.47%)207.2 W~ ≤5%
400 mm²570 A445 A1.41 V (2.94%)46.6 V2.33 V (4.85%)155.4 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 110A at 120 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 110A over 120m at 48V (voltage drop: 1.41V or 2.94%).

What is the power capacity of 110A at 48V?

At unity power factor, 110A at 48V supports 5.28 kW with a standard 110A circuit breaker.