110 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 10.19V (2.46%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.91V (2.63%)
Voltage at Load404.8 VLine Loss: 1942.0 W
Max Power & Breaker79.07 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A815.45 V (196.49%)0.0 V1345.11 V (324.12%)155364.0 WDrop High
2.5 mm²24 A18 A489.27 V (117.9%)0.0 V807.07 V (194.47%)93218.4 WDrop High
4 mm²32 A25 A305.79 V (73.69%)109.2 V504.42 V (121.55%)58261.5 WDrop High
6 mm²41 A32 A203.86 V (49.12%)211.1 V336.28 V (81.03%)38841.0 WDrop High
10 mm²57 A44 A122.32 V (29.47%)292.7 V201.77 V (48.62%)23304.6 WDrop High
16 mm²76 A59 A76.45 V (18.42%)338.6 V126.1 V (30.39%)14565.4 WDrop High
25 mm²101 A78 A48.93 V (11.79%)366.1 V80.71 V (19.45%)9321.8 WDrop High
35 mm²125 A97 A34.95 V (8.42%)380.1 V57.65 V (13.89%)6658.5 WDrop High
50 mm²151 A118 A24.46 V (5.89%)390.5 V40.35 V (9.72%)4660.9 WDrop High
70 mm²192 A150 A17.47 V (4.21%)397.5 V28.82 V (6.95%)3329.2 W~ ≤5%
95 mm²232 A181 A12.88 V (3.1%)402.1 V21.24 V (5.12%)2453.1 W~ ≤5%
120 mm²269 A210 A10.19 V (2.46%)404.8 V16.81 V (4.05%)1942.0 W✓ OK (≤3%)
150 mm²309 A241 A8.15 V (1.96%)406.8 V13.45 V (3.24%)1553.6 W✓ OK (≤3%)
185 mm²353 A275 A6.61 V (1.59%)408.4 V10.91 V (2.63%)1259.7 W✓ OK (≤3%)
240 mm²415 A324 A5.1 V (1.23%)409.9 V8.41 V (2.03%)971.0 W✓ OK (≤3%)
300 mm²477 A372 A4.08 V (0.98%)410.9 V6.73 V (1.62%)776.8 W✓ OK (≤3%)
400 mm²570 A445 A3.06 V (0.74%)411.9 V5.04 V (1.22%)582.6 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 110A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 110A over 300m at 415V (voltage drop: 10.19V or 2.46%).

What is the power capacity of 110A at 415V?

At unity power factor, 110A at 415V supports 79.07 kW with a standard 110A circuit breaker.