200 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 12.02V (2.9%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 12.23V (2.95%)
Voltage at Load403.0 VLine Loss: 4164.3 W
Max Power & Breaker143.76 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1482.64 V (357.26%)0.0 V2445.66 V (589.31%)513600.0 WDrop High
2.5 mm²24 A18 A889.58 V (214.36%)0.0 V1467.39 V (353.59%)308160.0 WDrop High
4 mm²32 A25 A555.99 V (133.97%)0.0 V917.12 V (220.99%)192600.0 WDrop High
6 mm²41 A32 A370.66 V (89.32%)44.3 V611.41 V (147.33%)128400.0 WDrop High
10 mm²57 A44 A222.4 V (53.59%)192.6 V366.85 V (88.4%)77040.0 WDrop High
16 mm²76 A59 A139.0 V (33.49%)276.0 V229.28 V (55.25%)48150.0 WDrop High
25 mm²101 A78 A88.96 V (21.44%)326.0 V146.74 V (35.36%)30816.0 WDrop High
35 mm²125 A97 A63.54 V (15.31%)351.5 V104.81 V (25.26%)22011.4 WDrop High
50 mm²151 A118 A44.48 V (10.72%)370.5 V73.37 V (17.68%)15408.0 WDrop High
70 mm²192 A150 A31.77 V (7.66%)383.2 V52.41 V (12.63%)11005.7 WDrop High
95 mm²232 A181 A23.41 V (5.64%)391.6 V38.62 V (9.3%)8109.5 WDrop High
120 mm²269 A210 A18.53 V (4.47%)396.5 V30.57 V (7.37%)6420.0 W~ ≤5%
150 mm²309 A241 A14.83 V (3.57%)400.2 V24.46 V (5.89%)5136.0 W~ ≤5%
185 mm²353 A275 A12.02 V (2.9%)403.0 V19.83 V (4.78%)4164.3 W✓ OK (≤3%)
240 mm²415 A324 A9.27 V (2.23%)405.7 V15.29 V (3.68%)3210.0 W✓ OK (≤3%)
300 mm²477 A372 A7.41 V (1.79%)407.6 V12.23 V (2.95%)2568.0 W✓ OK (≤3%)
400 mm²570 A445 A5.56 V (1.34%)409.4 V9.17 V (2.21%)1926.0 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 200A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 200A over 300m at 415V (voltage drop: 12.02V or 2.9%).

What is the power capacity of 200A at 415V?

At unity power factor, 200A at 415V supports 143.76 kW with a standard 200A circuit breaker.