⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

40 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 8.9V (2.14%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 10.48V (2.53%)
Voltage at Load406.1 VLine Loss: 616.3 W
Max Power & Breaker28.75 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A296.53 V (71.45%)118.5 V489.13 V (117.86%)20544.0 WDrop High
2.5 mm²24 A18 A177.92 V (42.87%)237.1 V293.48 V (70.72%)12326.4 WDrop High
4 mm²32 A25 A111.2 V (26.79%)303.8 V183.42 V (44.2%)7704.0 WDrop High
6 mm²41 A32 A74.13 V (17.86%)340.9 V122.28 V (29.47%)5136.0 WDrop High
10 mm²57 A44 A44.48 V (10.72%)370.5 V73.37 V (17.68%)3081.6 WDrop High
16 mm²76 A59 A27.8 V (6.7%)387.2 V45.86 V (11.05%)1926.0 WDrop High
25 mm²101 A78 A17.79 V (4.29%)397.2 V29.35 V (7.07%)1232.6 W~ ≤5%
35 mm²125 A97 A12.71 V (3.06%)402.3 V20.96 V (5.05%)880.5 W~ ≤5%
50 mm²151 A118 A8.9 V (2.14%)406.1 V14.67 V (3.54%)616.3 W✓ OK (≤3%)
70 mm²192 A150 A6.35 V (1.53%)408.6 V10.48 V (2.53%)440.2 W✓ OK (≤3%)
95 mm²232 A181 A4.68 V (1.13%)410.3 V7.72 V (1.86%)324.4 W✓ OK (≤3%)
120 mm²269 A210 A3.71 V (0.89%)411.3 V6.11 V (1.47%)256.8 W✓ OK (≤3%)
150 mm²309 A241 A2.97 V (0.71%)412.0 V4.89 V (1.18%)205.4 W✓ OK (≤3%)
185 mm²353 A275 A2.4 V (0.58%)412.6 V3.97 V (0.96%)166.6 W✓ OK (≤3%)
240 mm²415 A324 A1.85 V (0.45%)413.1 V3.06 V (0.74%)128.4 W✓ OK (≤3%)
300 mm²477 A372 A1.48 V (0.36%)413.5 V2.45 V (0.59%)102.7 W✓ OK (≤3%)
400 mm²570 A445 A1.11 V (0.27%)413.9 V1.83 V (0.44%)77.0 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 40A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 40A over 300m at 415V (voltage drop: 8.9V or 2.14%).

What is the power capacity of 40A at 415V?

At unity power factor, 40A at 415V supports 28.75 kW with a standard 40A circuit breaker.