110 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 5.38V (2.34%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 6.54V (2.84%)
Voltage at Load224.6 VLine Loss: 591.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A251.09 V (109.17%)0.0 V414.19 V (180.08%)27620.3 WDrop High
2.5 mm²24 A18 A150.66 V (65.5%)79.3 V248.51 V (108.05%)16572.2 WDrop High
4 mm²32 A25 A94.16 V (40.94%)135.8 V155.32 V (67.53%)10357.6 WDrop High
6 mm²41 A32 A62.77 V (27.29%)167.2 V103.55 V (45.02%)6905.1 WDrop High
10 mm²57 A44 A37.66 V (16.38%)192.3 V62.13 V (27.01%)4143.0 WDrop High
16 mm²76 A59 A23.54 V (10.23%)206.5 V38.83 V (16.88%)2589.4 WDrop High
25 mm²101 A78 A15.07 V (6.55%)214.9 V24.85 V (10.8%)1657.2 WDrop High
35 mm²125 A97 A10.76 V (4.68%)219.2 V17.75 V (7.72%)1183.7 W~ ≤5%
50 mm²151 A118 A7.53 V (3.28%)222.5 V12.43 V (5.4%)828.6 W~ ≤5%
70 mm²192 A150 A5.38 V (2.34%)224.6 V8.88 V (3.86%)591.9 W✓ OK (≤3%)
95 mm²232 A181 A3.96 V (1.72%)226.0 V6.54 V (2.84%)436.1 W✓ OK (≤3%)
120 mm²269 A210 A3.14 V (1.36%)226.9 V5.18 V (2.25%)345.3 W✓ OK (≤3%)
150 mm²309 A241 A2.51 V (1.09%)227.5 V4.14 V (1.8%)276.2 W✓ OK (≤3%)
185 mm²353 A275 A2.04 V (0.89%)228.0 V3.36 V (1.46%)223.9 W✓ OK (≤3%)
240 mm²415 A324 A1.57 V (0.68%)228.4 V2.59 V (1.13%)172.6 W✓ OK (≤3%)
300 mm²477 A372 A1.26 V (0.55%)228.7 V2.07 V (0.9%)138.1 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (0.41%)229.1 V1.55 V (0.68%)103.6 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 110A at 80 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 110A over 80m at 230V (voltage drop: 5.38V or 2.34%).

What is the power capacity of 110A at 230V?

At unity power factor, 110A at 230V supports 25.3 kW with a standard 110A circuit breaker.