110 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 80 m (262.5 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.47V (1.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.55V (6.47%)
Voltage at Load23.5 VLine Loss: 51.8 W
Max Power & Breaker2.64 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 251.09 V (1046.22%) | 0.0 V | 414.19 V (1725.78%) | 27620.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 150.66 V (627.73%) | 0.0 V | 248.51 V (1035.47%) | 16572.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 94.16 V (392.33%) | 0.0 V | 155.32 V (647.17%) | 10357.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 62.77 V (261.56%) | 0.0 V | 103.55 V (431.44%) | 6905.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 37.66 V (156.93%) | 0.0 V | 62.13 V (258.87%) | 4143.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 23.54 V (98.08%) | 0.5 V | 38.83 V (161.79%) | 2589.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 15.07 V (62.77%) | 8.9 V | 24.85 V (103.55%) | 1657.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 10.76 V (44.84%) | 13.2 V | 17.75 V (73.96%) | 1183.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 7.53 V (31.39%) | 16.5 V | 12.43 V (51.77%) | 828.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 5.38 V (22.42%) | 18.6 V | 8.88 V (36.98%) | 591.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.96 V (16.52%) | 20.0 V | 6.54 V (27.25%) | 436.1 W | Drop High |
| 120 mm² | 269 A | 210 A | 3.14 V (13.08%) | 20.9 V | 5.18 V (21.57%) | 345.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.51 V (10.46%) | 21.5 V | 4.14 V (17.26%) | 276.2 W | Drop High |
| 185 mm² | 353 A | 275 A | 2.04 V (8.48%) | 22.0 V | 3.36 V (13.99%) | 223.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.57 V (6.54%) | 22.4 V | 2.59 V (10.79%) | 172.6 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.26 V (5.23%) | 22.7 V | 2.07 V (8.63%) | 138.1 W | Drop High |
| 400 mm² | 570 A | 445 A | 0.94 V (3.92%) | 23.1 V | 1.55 V (6.47%) | 103.6 W | ~ ≤5% |
FAQ — 110 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 110A at 80 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 110A over 80m at 24V (voltage drop: 0.47V or 1.96%).
What is the power capacity of 110A at 24V?
At unity power factor, 110A at 24V supports 2.64 kW with a standard 110A circuit breaker.
Related Lengths & Currents (24V)
110A · 5m (24V)110A · 10m (24V)110A · 15m (24V)110A · 20m (24V)110A · 25m (24V)110A · 30m (24V)110A · 35m (24V)110A · 40m (24V)110A · 45m (24V)110A · 50m (24V)110A · 60m (24V)110A · 70m (24V)10A · 80m (24V)16A · 80m (24V)20A · 80m (24V)25A · 80m (24V)32A · 80m (24V)40A · 80m (24V)50A · 80m (24V)63A · 80m (24V)80A · 80m (24V)100A · 80m (24V)125A · 80m (24V)160A · 80m (24V)200A · 80m (24V)