15 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 25 m (82.0 ft).
Copper Cable (≤3% Drop)2.5 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 6.62V (2.88%)
Voltage at Load223.6 VLine Loss: 96.3 W
Max Power & Breaker3.45 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 10.7 V (4.65%) | 219.3 V | 17.65 V (7.67%) | 160.5 W | ~ ≤5% |
| 2.5 mm² | 24 A | 18 A | 6.42 V (2.79%) | 223.6 V | 10.59 V (4.6%) | 96.3 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 4.01 V (1.74%) | 226.0 V | 6.62 V (2.88%) | 60.2 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.67 V (1.16%) | 227.3 V | 4.41 V (1.92%) | 40.1 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.6 V (0.7%) | 228.4 V | 2.65 V (1.15%) | 24.1 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.0 V (0.44%) | 229.0 V | 1.65 V (0.72%) | 15.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.64 V (0.28%) | 229.4 V | 1.06 V (0.46%) | 9.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.46 V (0.2%) | 229.5 V | 0.76 V (0.33%) | 6.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.32 V (0.14%) | 229.7 V | 0.53 V (0.23%) | 4.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.23 V (0.1%) | 229.8 V | 0.38 V (0.16%) | 3.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.17 V (0.07%) | 229.8 V | 0.28 V (0.12%) | 2.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.13 V (0.06%) | 229.9 V | 0.22 V (0.1%) | 2.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.11 V (0.05%) | 229.9 V | 0.18 V (0.08%) | 1.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.09 V (0.04%) | 229.9 V | 0.14 V (0.06%) | 1.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.07 V (0.03%) | 229.9 V | 0.11 V (0.05%) | 1.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.05 V (0.02%) | 229.9 V | 0.09 V (0.04%) | 0.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.04 V (0.02%) | 230.0 V | 0.07 V (0.03%) | 0.6 W | ✓ OK (≤3%) |
FAQ — 15 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 15A at 25 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 15A over 25m at 230V (voltage drop: 6.42V or 2.79%).
What is the power capacity of 15A at 230V?
At unity power factor, 15A at 230V supports 3.45 kW with a standard 15A circuit breaker.
Related Lengths & Currents (230V)
15A · 5m (230V)15A · 10m (230V)15A · 15m (230V)15A · 20m (230V)15A · 30m (230V)15A · 35m (230V)15A · 40m (230V)15A · 45m (230V)15A · 50m (230V)15A · 60m (230V)15A · 70m (230V)10A · 25m (230V)16A · 25m (230V)20A · 25m (230V)25A · 25m (230V)32A · 25m (230V)40A · 25m (230V)50A · 25m (230V)63A · 25m (230V)80A · 25m (230V)100A · 25m (230V)125A · 25m (230V)160A · 25m (230V)200A · 25m (230V)