15 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 6.62V (2.88%)
Voltage at Load223.6 VLine Loss: 96.3 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A10.7 V (4.65%)219.3 V17.65 V (7.67%)160.5 W~ ≤5%
2.5 mm²24 A18 A6.42 V (2.79%)223.6 V10.59 V (4.6%)96.3 W✓ OK (≤3%)
4 mm²32 A25 A4.01 V (1.74%)226.0 V6.62 V (2.88%)60.2 W✓ OK (≤3%)
6 mm²41 A32 A2.67 V (1.16%)227.3 V4.41 V (1.92%)40.1 W✓ OK (≤3%)
10 mm²57 A44 A1.6 V (0.7%)228.4 V2.65 V (1.15%)24.1 W✓ OK (≤3%)
16 mm²76 A59 A1.0 V (0.44%)229.0 V1.65 V (0.72%)15.0 W✓ OK (≤3%)
25 mm²101 A78 A0.64 V (0.28%)229.4 V1.06 V (0.46%)9.6 W✓ OK (≤3%)
35 mm²125 A97 A0.46 V (0.2%)229.5 V0.76 V (0.33%)6.9 W✓ OK (≤3%)
50 mm²151 A118 A0.32 V (0.14%)229.7 V0.53 V (0.23%)4.8 W✓ OK (≤3%)
70 mm²192 A150 A0.23 V (0.1%)229.8 V0.38 V (0.16%)3.4 W✓ OK (≤3%)
95 mm²232 A181 A0.17 V (0.07%)229.8 V0.28 V (0.12%)2.5 W✓ OK (≤3%)
120 mm²269 A210 A0.13 V (0.06%)229.9 V0.22 V (0.1%)2.0 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.05%)229.9 V0.18 V (0.08%)1.6 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.04%)229.9 V0.14 V (0.06%)1.3 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.0 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.02%)229.9 V0.09 V (0.04%)0.8 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.6 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 15A at 25 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 15A over 25m at 230V (voltage drop: 6.42V or 2.79%).

What is the power capacity of 15A at 230V?

At unity power factor, 15A at 230V supports 3.45 kW with a standard 15A circuit breaker.