125 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 3.82V (1.66%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 3.15V (1.37%)
Voltage at Load226.2 VLine Loss: 477.7 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A89.17 V (38.77%)140.8 V147.08 V (63.95%)11145.8 WDrop High
2.5 mm²24 A18 A53.5 V (23.26%)176.5 V88.25 V (38.37%)6687.5 WDrop High
4 mm²32 A25 A33.44 V (14.54%)196.6 V55.16 V (23.98%)4179.7 WDrop High
6 mm²41 A32 A22.29 V (9.69%)207.7 V36.77 V (15.99%)2786.5 WDrop High
10 mm²57 A44 A13.37 V (5.82%)216.6 V22.06 V (9.59%)1671.9 WDrop High
16 mm²76 A59 A8.36 V (3.63%)221.6 V13.79 V (6.0%)1044.9 WDrop High
25 mm²101 A78 A5.35 V (2.33%)224.7 V8.82 V (3.84%)668.7 WDrop High
35 mm²125 A97 A3.82 V (1.66%)226.2 V6.3 V (2.74%)477.7 W✓ OK (≤3%)
50 mm²151 A118 A2.67 V (1.16%)227.3 V4.41 V (1.92%)334.4 W✓ OK (≤3%)
70 mm²192 A150 A1.91 V (0.83%)228.1 V3.15 V (1.37%)238.8 W✓ OK (≤3%)
95 mm²232 A181 A1.41 V (0.61%)228.6 V2.32 V (1.01%)176.0 W✓ OK (≤3%)
120 mm²269 A210 A1.11 V (0.48%)228.9 V1.84 V (0.8%)139.3 W✓ OK (≤3%)
150 mm²309 A241 A0.89 V (0.39%)229.1 V1.47 V (0.64%)111.5 W✓ OK (≤3%)
185 mm²353 A275 A0.72 V (0.31%)229.3 V1.19 V (0.52%)90.4 W✓ OK (≤3%)
240 mm²415 A324 A0.56 V (0.24%)229.4 V0.92 V (0.4%)69.7 W✓ OK (≤3%)
300 mm²477 A372 A0.45 V (0.19%)229.6 V0.74 V (0.32%)55.7 W✓ OK (≤3%)
400 mm²570 A445 A0.33 V (0.15%)229.7 V0.55 V (0.24%)41.8 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 125A at 25 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 25m at 230V (voltage drop: 3.82V or 1.66%).

What is the power capacity of 125A at 230V?

At unity power factor, 125A at 230V supports 28.75 kW with a standard 125A circuit breaker.