⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

16 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.71V (2.05%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.41 V (4.96%)218.6 V18.83 V (8.19%)182.6 W~ ≤5%
2.5 mm²24 A18 A6.85 V (2.98%)223.2 V11.3 V (4.91%)109.6 W✓ OK (≤3%)
4 mm²32 A25 A4.28 V (1.86%)225.7 V7.06 V (3.07%)68.5 W✓ OK (≤3%)
6 mm²41 A32 A2.85 V (1.24%)227.1 V4.71 V (2.05%)45.7 W✓ OK (≤3%)
10 mm²57 A44 A1.71 V (0.74%)228.3 V2.82 V (1.23%)27.4 W✓ OK (≤3%)
16 mm²76 A59 A1.07 V (0.47%)228.9 V1.76 V (0.77%)17.1 W✓ OK (≤3%)
25 mm²101 A78 A0.68 V (0.3%)229.3 V1.13 V (0.49%)11.0 W✓ OK (≤3%)
35 mm²125 A97 A0.49 V (0.21%)229.5 V0.81 V (0.35%)7.8 W✓ OK (≤3%)
50 mm²151 A118 A0.34 V (0.15%)229.7 V0.56 V (0.25%)5.5 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.11%)229.8 V0.4 V (0.18%)3.9 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.08%)229.8 V0.3 V (0.13%)2.9 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.06%)229.9 V0.24 V (0.1%)2.3 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.05%)229.9 V0.19 V (0.08%)1.8 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.5 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.03%)229.9 V0.12 V (0.05%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.02%)229.9 V0.09 V (0.04%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.7 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 25 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 16A at 25 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 16A over 25m at 230V (voltage drop: 6.85V or 2.98%).

What is the power capacity of 16A at 230V?

At unity power factor, 16A at 230V supports 3.68 kW with a standard 16A circuit breaker.