15 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 5.5V (2.39%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 6.69V (2.91%)
Voltage at Load224.5 VLine Loss: 82.5 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A256.8 V (111.65%)0.0 V423.6 V (184.17%)3852.0 WDrop High
2.5 mm²24 A18 A154.08 V (66.99%)75.9 V254.16 V (110.5%)2311.2 WDrop High
4 mm²32 A25 A96.3 V (41.87%)133.7 V158.85 V (69.07%)1444.5 WDrop High
6 mm²41 A32 A64.2 V (27.91%)165.8 V105.9 V (46.04%)963.0 WDrop High
10 mm²57 A44 A38.52 V (16.75%)191.5 V63.54 V (27.63%)577.8 WDrop High
16 mm²76 A59 A24.07 V (10.47%)205.9 V39.71 V (17.27%)361.1 WDrop High
25 mm²101 A78 A15.41 V (6.7%)214.6 V25.42 V (11.05%)231.1 WDrop High
35 mm²125 A97 A11.01 V (4.79%)219.0 V18.15 V (7.89%)165.1 W~ ≤5%
50 mm²151 A118 A7.7 V (3.35%)222.3 V12.71 V (5.53%)115.6 W~ ≤5%
70 mm²192 A150 A5.5 V (2.39%)224.5 V9.08 V (3.95%)82.5 W✓ OK (≤3%)
95 mm²232 A181 A4.05 V (1.76%)225.9 V6.69 V (2.91%)60.8 W✓ OK (≤3%)
120 mm²269 A210 A3.21 V (1.4%)226.8 V5.29 V (2.3%)48.1 W✓ OK (≤3%)
150 mm²309 A241 A2.57 V (1.12%)227.4 V4.24 V (1.84%)38.5 W✓ OK (≤3%)
185 mm²353 A275 A2.08 V (0.91%)227.9 V3.43 V (1.49%)31.2 W✓ OK (≤3%)
240 mm²415 A324 A1.6 V (0.7%)228.4 V2.65 V (1.15%)24.1 W✓ OK (≤3%)
300 mm²477 A372 A1.28 V (0.56%)228.7 V2.12 V (0.92%)19.3 W✓ OK (≤3%)
400 mm²570 A445 A0.96 V (0.42%)229.0 V1.59 V (0.69%)14.4 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 15A at 600 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 15A over 600m at 230V (voltage drop: 5.5V or 2.39%).

What is the power capacity of 15A at 230V?

At unity power factor, 15A at 230V supports 3.45 kW with a standard 15A circuit breaker.