150 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.62V (2.88%)
Voltage at Load223.6 VLine Loss: 963.0 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A642.0 V (279.13%)0.0 V1059.0 V (460.43%)96300.0 WDrop High
2.5 mm²24 A18 A385.2 V (167.48%)0.0 V635.4 V (276.26%)57780.0 WDrop High
4 mm²32 A25 A240.75 V (104.67%)0.0 V397.12 V (172.66%)36112.5 WDrop High
6 mm²41 A32 A160.5 V (69.78%)69.5 V264.75 V (115.11%)24075.0 WDrop High
10 mm²57 A44 A96.3 V (41.87%)133.7 V158.85 V (69.07%)14445.0 WDrop High
16 mm²76 A59 A60.19 V (26.17%)169.8 V99.28 V (43.17%)9028.1 WDrop High
25 mm²101 A78 A38.52 V (16.75%)191.5 V63.54 V (27.63%)5778.0 WDrop High
35 mm²125 A97 A27.51 V (11.96%)202.5 V45.39 V (19.73%)4127.1 WDrop High
50 mm²151 A118 A19.26 V (8.37%)210.7 V31.77 V (13.81%)2889.0 WDrop High
70 mm²192 A150 A13.76 V (5.98%)216.2 V22.69 V (9.87%)2063.6 WDrop High
95 mm²232 A181 A10.14 V (4.41%)219.9 V16.72 V (7.27%)1520.5 W~ ≤5%
120 mm²269 A210 A8.03 V (3.49%)222.0 V13.24 V (5.76%)1203.8 W~ ≤5%
150 mm²309 A241 A6.42 V (2.79%)223.6 V10.59 V (4.6%)963.0 W✓ OK (≤3%)
185 mm²353 A275 A5.21 V (2.26%)224.8 V8.59 V (3.73%)780.8 W✓ OK (≤3%)
240 mm²415 A324 A4.01 V (1.74%)226.0 V6.62 V (2.88%)601.9 W✓ OK (≤3%)
300 mm²477 A372 A3.21 V (1.4%)226.8 V5.29 V (2.3%)481.5 W✓ OK (≤3%)
400 mm²570 A445 A2.41 V (1.05%)227.6 V3.97 V (1.73%)361.1 W✓ OK (≤3%)

FAQ — 150 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 150A at 150 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 150A over 150m at 230V (voltage drop: 6.42V or 2.79%).

What is the power capacity of 150A at 230V?

At unity power factor, 150A at 230V supports 34.5 kW with a standard 150A circuit breaker.