150 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 5 m (16.4 ft).
Copper Cable (≤3% Drop)50 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.56V (2.32%)
Voltage at Load23.4 VLine Loss: 96.3 W
Max Power & Breaker3.6 kW150A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 21.4 V (89.17%) | 2.6 V | 35.3 V (147.08%) | 3210.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 12.84 V (53.5%) | 11.2 V | 21.18 V (88.25%) | 1926.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 8.03 V (33.44%) | 16.0 V | 13.24 V (55.16%) | 1203.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 5.35 V (22.29%) | 18.6 V | 8.82 V (36.77%) | 802.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 3.21 V (13.38%) | 20.8 V | 5.29 V (22.06%) | 481.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 2.01 V (8.36%) | 22.0 V | 3.31 V (13.79%) | 300.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 1.28 V (5.35%) | 22.7 V | 2.12 V (8.82%) | 192.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 0.92 V (3.82%) | 23.1 V | 1.51 V (6.3%) | 137.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 0.64 V (2.67%) | 23.4 V | 1.06 V (4.41%) | 96.3 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.46 V (1.91%) | 23.5 V | 0.76 V (3.15%) | 68.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.34 V (1.41%) | 23.7 V | 0.56 V (2.32%) | 50.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.27 V (1.11%) | 23.7 V | 0.44 V (1.84%) | 40.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.21 V (0.89%) | 23.8 V | 0.35 V (1.47%) | 32.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.17 V (0.72%) | 23.8 V | 0.29 V (1.19%) | 26.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.13 V (0.56%) | 23.9 V | 0.22 V (0.92%) | 20.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.11 V (0.45%) | 23.9 V | 0.18 V (0.74%) | 16.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.08 V (0.33%) | 23.9 V | 0.13 V (0.55%) | 12.0 W | ✓ OK (≤3%) |
FAQ — 150 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 150A at 5 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 150A over 5m at 24V (voltage drop: 0.64V or 2.67%).
What is the power capacity of 150A at 24V?
At unity power factor, 150A at 24V supports 3.6 kW with a standard 150A circuit breaker.
Related Lengths & Currents (24V)
150A · 10m (24V)150A · 15m (24V)150A · 20m (24V)150A · 25m (24V)150A · 30m (24V)150A · 35m (24V)150A · 40m (24V)150A · 45m (24V)150A · 50m (24V)150A · 60m (24V)150A · 70m (24V)10A · 5m (24V)16A · 5m (24V)20A · 5m (24V)25A · 5m (24V)32A · 5m (24V)40A · 5m (24V)50A · 5m (24V)63A · 5m (24V)80A · 5m (24V)100A · 5m (24V)125A · 5m (24V)160A · 5m (24V)200A · 5m (24V)