150 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 150 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.66V (2.76%)
Voltage at Load23.4 VLine Loss: 96.3 W
Max Power & Breaker3.6 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A64.2 V (267.5%)0.0 V105.9 V (441.25%)9630.0 WDrop High
2.5 mm²24 A18 A38.52 V (160.5%)0.0 V63.54 V (264.75%)5778.0 WDrop High
4 mm²32 A25 A24.07 V (100.31%)0.0 V39.71 V (165.47%)3611.2 WDrop High
6 mm²41 A32 A16.05 V (66.88%)7.9 V26.47 V (110.31%)2407.5 WDrop High
10 mm²57 A44 A9.63 V (40.13%)14.4 V15.88 V (66.19%)1444.5 WDrop High
16 mm²76 A59 A6.02 V (25.08%)18.0 V9.93 V (41.37%)902.8 WDrop High
25 mm²101 A78 A3.85 V (16.05%)20.1 V6.35 V (26.47%)577.8 WDrop High
35 mm²125 A97 A2.75 V (11.46%)21.2 V4.54 V (18.91%)412.7 WDrop High
50 mm²151 A118 A1.93 V (8.03%)22.1 V3.18 V (13.24%)288.9 WDrop High
70 mm²192 A150 A1.38 V (5.73%)22.6 V2.27 V (9.46%)206.4 WDrop High
95 mm²232 A181 A1.01 V (4.22%)23.0 V1.67 V (6.97%)152.1 W~ ≤5%
120 mm²269 A210 A0.8 V (3.34%)23.2 V1.32 V (5.52%)120.4 W~ ≤5%
150 mm²309 A241 A0.64 V (2.67%)23.4 V1.06 V (4.41%)96.3 W✓ OK (≤3%)
185 mm²353 A275 A0.52 V (2.17%)23.5 V0.86 V (3.58%)78.1 W✓ OK (≤3%)
240 mm²415 A324 A0.4 V (1.67%)23.6 V0.66 V (2.76%)60.2 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (1.34%)23.7 V0.53 V (2.21%)48.1 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (1.0%)23.8 V0.4 V (1.65%)36.1 W✓ OK (≤3%)

FAQ — 150 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 150A at 15 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 150A over 15m at 24V (voltage drop: 0.64V or 2.67%).

What is the power capacity of 150A at 24V?

At unity power factor, 150A at 24V supports 3.6 kW with a standard 150A circuit breaker.