⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

160 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 11.86V (2.86%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.67V (3.54%)
Voltage at Load403.1 VLine Loss: 3287.0 W
Max Power & Breaker115.01 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2372.22 V (571.62%)0.0 V3913.05 V (942.9%)657408.0 WDrop High
2.5 mm²24 A18 A1423.33 V (342.97%)0.0 V2347.83 V (565.74%)394444.8 WDrop High
4 mm²32 A25 A889.58 V (214.36%)0.0 V1467.39 V (353.59%)246528.0 WDrop High
6 mm²41 A32 A593.05 V (142.9%)0.0 V978.26 V (235.73%)164352.0 WDrop High
10 mm²57 A44 A355.83 V (85.74%)59.2 V586.96 V (141.44%)98611.2 WDrop High
16 mm²76 A59 A222.4 V (53.59%)192.6 V366.85 V (88.4%)61632.0 WDrop High
25 mm²101 A78 A142.33 V (34.3%)272.7 V234.78 V (56.57%)39444.5 WDrop High
35 mm²125 A97 A101.67 V (24.5%)313.3 V167.7 V (40.41%)28174.6 WDrop High
50 mm²151 A118 A71.17 V (17.15%)343.8 V117.39 V (28.29%)19722.2 WDrop High
70 mm²192 A150 A50.83 V (12.25%)364.2 V83.85 V (20.21%)14087.3 WDrop High
95 mm²232 A181 A37.46 V (9.03%)377.5 V61.78 V (14.89%)10380.1 WDrop High
120 mm²269 A210 A29.65 V (7.15%)385.3 V48.91 V (11.79%)8217.6 WDrop High
150 mm²309 A241 A23.72 V (5.72%)391.3 V39.13 V (9.43%)6574.1 WDrop High
185 mm²353 A275 A19.23 V (4.63%)395.8 V31.73 V (7.65%)5330.3 W~ ≤5%
240 mm²415 A324 A14.83 V (3.57%)400.2 V24.46 V (5.89%)4108.8 W~ ≤5%
300 mm²477 A372 A11.86 V (2.86%)403.1 V19.57 V (4.71%)3287.0 W✓ OK (≤3%)
400 mm²570 A445 A8.9 V (2.14%)406.1 V14.67 V (3.54%)2465.3 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 160A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 160A over 600m at 415V (voltage drop: 11.86V or 2.86%).

What is the power capacity of 160A at 415V?

At unity power factor, 160A at 415V supports 115.01 kW with a standard 160A circuit breaker.