125 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 11.58V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.46V (2.76%)
Voltage at Load403.4 VLine Loss: 2507.8 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1853.29 V (446.58%)0.0 V3057.07 V (736.64%)401250.0 WDrop High
2.5 mm²24 A18 A1111.98 V (267.95%)0.0 V1834.24 V (441.99%)240750.0 WDrop High
4 mm²32 A25 A694.99 V (167.47%)0.0 V1146.4 V (276.24%)150468.8 WDrop High
6 mm²41 A32 A463.32 V (111.64%)0.0 V764.27 V (184.16%)100312.5 WDrop High
10 mm²57 A44 A277.99 V (66.99%)137.0 V458.56 V (110.5%)60187.5 WDrop High
16 mm²76 A59 A173.75 V (41.87%)241.3 V286.6 V (69.06%)37617.2 WDrop High
25 mm²101 A78 A111.2 V (26.79%)303.8 V183.42 V (44.2%)24075.0 WDrop High
35 mm²125 A97 A79.43 V (19.14%)335.6 V131.02 V (31.57%)17196.4 WDrop High
50 mm²151 A118 A55.6 V (13.4%)359.4 V91.71 V (22.1%)12037.5 WDrop High
70 mm²192 A150 A39.71 V (9.57%)375.3 V65.51 V (15.79%)8598.2 WDrop High
95 mm²232 A181 A29.26 V (7.05%)385.7 V48.27 V (11.63%)6335.5 WDrop High
120 mm²269 A210 A23.17 V (5.58%)391.8 V38.21 V (9.21%)5015.6 WDrop High
150 mm²309 A241 A18.53 V (4.47%)396.5 V30.57 V (7.37%)4012.5 W~ ≤5%
185 mm²353 A275 A15.03 V (3.62%)400.0 V24.79 V (5.97%)3253.4 W~ ≤5%
240 mm²415 A324 A11.58 V (2.79%)403.4 V19.11 V (4.6%)2507.8 W✓ OK (≤3%)
300 mm²477 A372 A9.27 V (2.23%)405.7 V15.29 V (3.68%)2006.2 W✓ OK (≤3%)
400 mm²570 A445 A6.95 V (1.67%)408.1 V11.46 V (2.76%)1504.7 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 125A over 600m at 415V (voltage drop: 11.58V or 2.79%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.