32 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 10.17V (2.45%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 12.36V (2.98%)
Voltage at Load404.8 VLine Loss: 563.5 W
Max Power & Breaker23.0 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A474.44 V (114.32%)0.0 V782.61 V (188.58%)26296.3 WDrop High
2.5 mm²24 A18 A284.67 V (68.59%)130.3 V469.57 V (113.15%)15777.8 WDrop High
4 mm²32 A25 A177.92 V (42.87%)237.1 V293.48 V (70.72%)9861.1 WDrop High
6 mm²41 A32 A118.61 V (28.58%)296.4 V195.65 V (47.15%)6574.1 WDrop High
10 mm²57 A44 A71.17 V (17.15%)343.8 V117.39 V (28.29%)3944.4 WDrop High
16 mm²76 A59 A44.48 V (10.72%)370.5 V73.37 V (17.68%)2465.3 WDrop High
25 mm²101 A78 A28.47 V (6.86%)386.5 V46.96 V (11.31%)1577.8 WDrop High
35 mm²125 A97 A20.33 V (4.9%)394.7 V33.54 V (8.08%)1127.0 W~ ≤5%
50 mm²151 A118 A14.23 V (3.43%)400.8 V23.48 V (5.66%)788.9 W~ ≤5%
70 mm²192 A150 A10.17 V (2.45%)404.8 V16.77 V (4.04%)563.5 W✓ OK (≤3%)
95 mm²232 A181 A7.49 V (1.81%)407.5 V12.36 V (2.98%)415.2 W✓ OK (≤3%)
120 mm²269 A210 A5.93 V (1.43%)409.1 V9.78 V (2.36%)328.7 W✓ OK (≤3%)
150 mm²309 A241 A4.74 V (1.14%)410.3 V7.83 V (1.89%)263.0 W✓ OK (≤3%)
185 mm²353 A275 A3.85 V (0.93%)411.2 V6.35 V (1.53%)213.2 W✓ OK (≤3%)
240 mm²415 A324 A2.97 V (0.71%)412.0 V4.89 V (1.18%)164.4 W✓ OK (≤3%)
300 mm²477 A372 A2.37 V (0.57%)412.6 V3.91 V (0.94%)131.5 W✓ OK (≤3%)
400 mm²570 A445 A1.78 V (0.43%)413.2 V2.93 V (0.71%)98.6 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 32A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 32A over 600m at 415V (voltage drop: 10.17V or 2.45%).

What is the power capacity of 32A at 415V?

At unity power factor, 32A at 415V supports 23.0 kW with a standard 32A circuit breaker.