160 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 19.23V (2.79%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 19.57V (2.84%)
Voltage at Load670.8 VLine Loss: 5330.3 W
Max Power & Breaker191.22 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2372.22 V (343.8%)0.0 V3913.05 V (567.11%)657408.0 WDrop High
2.5 mm²24 A18 A1423.33 V (206.28%)0.0 V2347.83 V (340.27%)394444.8 WDrop High
4 mm²32 A25 A889.58 V (128.92%)0.0 V1467.39 V (212.67%)246528.0 WDrop High
6 mm²41 A32 A593.05 V (85.95%)96.9 V978.26 V (141.78%)164352.0 WDrop High
10 mm²57 A44 A355.83 V (51.57%)334.2 V586.96 V (85.07%)98611.2 WDrop High
16 mm²76 A59 A222.4 V (32.23%)467.6 V366.85 V (53.17%)61632.0 WDrop High
25 mm²101 A78 A142.33 V (20.63%)547.7 V234.78 V (34.03%)39444.5 WDrop High
35 mm²125 A97 A101.67 V (14.73%)588.3 V167.7 V (24.3%)28174.6 WDrop High
50 mm²151 A118 A71.17 V (10.31%)618.8 V117.39 V (17.01%)19722.2 WDrop High
70 mm²192 A150 A50.83 V (7.37%)639.2 V83.85 V (12.15%)14087.3 WDrop High
95 mm²232 A181 A37.46 V (5.43%)652.5 V61.78 V (8.95%)10380.1 WDrop High
120 mm²269 A210 A29.65 V (4.3%)660.3 V48.91 V (7.09%)8217.6 W~ ≤5%
150 mm²309 A241 A23.72 V (3.44%)666.3 V39.13 V (5.67%)6574.1 W~ ≤5%
185 mm²353 A275 A19.23 V (2.79%)670.8 V31.73 V (4.6%)5330.3 W✓ OK (≤3%)
240 mm²415 A324 A14.83 V (2.15%)675.2 V24.46 V (3.54%)4108.8 W✓ OK (≤3%)
300 mm²477 A372 A11.86 V (1.72%)678.1 V19.57 V (2.84%)3287.0 W✓ OK (≤3%)
400 mm²570 A445 A8.9 V (1.29%)681.1 V14.67 V (2.13%)2465.3 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 160A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 160A over 600m at 690V (voltage drop: 19.23V or 2.79%).

What is the power capacity of 160A at 690V?

At unity power factor, 160A at 690V supports 191.22 kW with a standard 160A circuit breaker.