20 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 17.79V (2.58%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 14.67V (2.13%)
Voltage at Load672.2 VLine Loss: 616.3 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A296.53 V (42.97%)393.5 V489.13 V (70.89%)10272.0 WDrop High
2.5 mm²24 A18 A177.92 V (25.78%)512.1 V293.48 V (42.53%)6163.2 WDrop High
4 mm²32 A25 A111.2 V (16.12%)578.8 V183.42 V (26.58%)3852.0 WDrop High
6 mm²41 A32 A74.13 V (10.74%)615.9 V122.28 V (17.72%)2568.0 WDrop High
10 mm²57 A44 A44.48 V (6.45%)645.5 V73.37 V (10.63%)1540.8 WDrop High
16 mm²76 A59 A27.8 V (4.03%)662.2 V45.86 V (6.65%)963.0 W~ ≤5%
25 mm²101 A78 A17.79 V (2.58%)672.2 V29.35 V (4.25%)616.3 W✓ OK (≤3%)
35 mm²125 A97 A12.71 V (1.84%)677.3 V20.96 V (3.04%)440.2 W✓ OK (≤3%)
50 mm²151 A118 A8.9 V (1.29%)681.1 V14.67 V (2.13%)308.2 W✓ OK (≤3%)
70 mm²192 A150 A6.35 V (0.92%)683.6 V10.48 V (1.52%)220.1 W✓ OK (≤3%)
95 mm²232 A181 A4.68 V (0.68%)685.3 V7.72 V (1.12%)162.2 W✓ OK (≤3%)
120 mm²269 A210 A3.71 V (0.54%)686.3 V6.11 V (0.89%)128.4 W✓ OK (≤3%)
150 mm²309 A241 A2.97 V (0.43%)687.0 V4.89 V (0.71%)102.7 W✓ OK (≤3%)
185 mm²353 A275 A2.4 V (0.35%)687.6 V3.97 V (0.57%)83.3 W✓ OK (≤3%)
240 mm²415 A324 A1.85 V (0.27%)688.1 V3.06 V (0.44%)64.2 W✓ OK (≤3%)
300 mm²477 A372 A1.48 V (0.21%)688.5 V2.45 V (0.35%)51.4 W✓ OK (≤3%)
400 mm²570 A445 A1.11 V (0.16%)688.9 V1.83 V (0.27%)38.5 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 20A over 600m at 690V (voltage drop: 17.79V or 2.58%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.