32 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 20.33V (2.95%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 16.77V (2.43%)
Voltage at Load669.7 VLine Loss: 1127.0 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A474.44 V (68.76%)215.6 V782.61 V (113.42%)26296.3 WDrop High
2.5 mm²24 A18 A284.67 V (41.26%)405.3 V469.57 V (68.05%)15777.8 WDrop High
4 mm²32 A25 A177.92 V (25.78%)512.1 V293.48 V (42.53%)9861.1 WDrop High
6 mm²41 A32 A118.61 V (17.19%)571.4 V195.65 V (28.36%)6574.1 WDrop High
10 mm²57 A44 A71.17 V (10.31%)618.8 V117.39 V (17.01%)3944.4 WDrop High
16 mm²76 A59 A44.48 V (6.45%)645.5 V73.37 V (10.63%)2465.3 WDrop High
25 mm²101 A78 A28.47 V (4.13%)661.5 V46.96 V (6.81%)1577.8 W~ ≤5%
35 mm²125 A97 A20.33 V (2.95%)669.7 V33.54 V (4.86%)1127.0 W✓ OK (≤3%)
50 mm²151 A118 A14.23 V (2.06%)675.8 V23.48 V (3.4%)788.9 W✓ OK (≤3%)
70 mm²192 A150 A10.17 V (1.47%)679.8 V16.77 V (2.43%)563.5 W✓ OK (≤3%)
95 mm²232 A181 A7.49 V (1.09%)682.5 V12.36 V (1.79%)415.2 W✓ OK (≤3%)
120 mm²269 A210 A5.93 V (0.86%)684.1 V9.78 V (1.42%)328.7 W✓ OK (≤3%)
150 mm²309 A241 A4.74 V (0.69%)685.3 V7.83 V (1.13%)263.0 W✓ OK (≤3%)
185 mm²353 A275 A3.85 V (0.56%)686.2 V6.35 V (0.92%)213.2 W✓ OK (≤3%)
240 mm²415 A324 A2.97 V (0.43%)687.0 V4.89 V (0.71%)164.4 W✓ OK (≤3%)
300 mm²477 A372 A2.37 V (0.34%)687.6 V3.91 V (0.57%)131.5 W✓ OK (≤3%)
400 mm²570 A445 A1.78 V (0.26%)688.2 V2.93 V (0.43%)98.6 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 32A over 600m at 690V (voltage drop: 20.33V or 2.95%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.