160 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 6.78V (1.63%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 8.24V (1.99%)
Voltage at Load408.2 VLine Loss: 1878.3 W
Max Power & Breaker115.01 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A316.3 V (76.22%)98.7 V521.74 V (125.72%)87654.4 WDrop High
2.5 mm²24 A18 A189.78 V (45.73%)225.2 V313.04 V (75.43%)52592.6 WDrop High
4 mm²32 A25 A118.61 V (28.58%)296.4 V195.65 V (47.15%)32870.4 WDrop High
6 mm²41 A32 A79.07 V (19.05%)335.9 V130.43 V (31.43%)21913.6 WDrop High
10 mm²57 A44 A47.44 V (11.43%)367.6 V78.26 V (18.86%)13148.2 WDrop High
16 mm²76 A59 A29.65 V (7.15%)385.3 V48.91 V (11.79%)8217.6 WDrop High
25 mm²101 A78 A18.98 V (4.57%)396.0 V31.3 V (7.54%)5259.3 WDrop High
35 mm²125 A97 A13.56 V (3.27%)401.4 V22.36 V (5.39%)3756.6 WDrop High
50 mm²151 A118 A9.49 V (2.29%)405.5 V15.65 V (3.77%)2629.6 WDrop High
70 mm²192 A150 A6.78 V (1.63%)408.2 V11.18 V (2.69%)1878.3 W✓ OK (≤3%)
95 mm²232 A181 A4.99 V (1.2%)410.0 V8.24 V (1.99%)1384.0 W✓ OK (≤3%)
120 mm²269 A210 A3.95 V (0.95%)411.0 V6.52 V (1.57%)1095.7 W✓ OK (≤3%)
150 mm²309 A241 A3.16 V (0.76%)411.8 V5.22 V (1.26%)876.5 W✓ OK (≤3%)
185 mm²353 A275 A2.56 V (0.62%)412.4 V4.23 V (1.02%)710.7 W✓ OK (≤3%)
240 mm²415 A324 A1.98 V (0.48%)413.0 V3.26 V (0.79%)547.8 W✓ OK (≤3%)
300 mm²477 A372 A1.58 V (0.38%)413.4 V2.61 V (0.63%)438.3 W✓ OK (≤3%)
400 mm²570 A445 A1.19 V (0.29%)413.8 V1.96 V (0.47%)328.7 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 160A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 160A over 80m at 415V (voltage drop: 6.78V or 1.63%).

What is the power capacity of 160A at 415V?

At unity power factor, 160A at 415V supports 115.01 kW with a standard 160A circuit breaker.