63 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 11.68V (2.81%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 12.33V (2.97%)
Voltage at Load403.3 VLine Loss: 1274.0 W
Max Power & Breaker45.28 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.54 V (30.01%)290.5 V205.44 V (49.5%)13589.9 WDrop High
2.5 mm²24 A18 A74.72 V (18.01%)340.3 V123.26 V (29.7%)8153.9 WDrop High
4 mm²32 A25 A46.7 V (11.25%)368.3 V77.04 V (18.56%)5096.2 WDrop High
6 mm²41 A32 A31.14 V (7.5%)383.9 V51.36 V (12.38%)3397.5 WDrop High
10 mm²57 A44 A18.68 V (4.5%)396.3 V30.82 V (7.43%)2038.5 WDrop High
16 mm²76 A59 A11.68 V (2.81%)403.3 V19.26 V (4.64%)1274.0 W✓ OK (≤3%)
25 mm²101 A78 A7.47 V (1.8%)407.5 V12.33 V (2.97%)815.4 W✓ OK (≤3%)
35 mm²125 A97 A5.34 V (1.29%)409.7 V8.8 V (2.12%)582.4 W✓ OK (≤3%)
50 mm²151 A118 A3.74 V (0.9%)411.3 V6.16 V (1.49%)407.7 W✓ OK (≤3%)
70 mm²192 A150 A2.67 V (0.64%)412.3 V4.4 V (1.06%)291.2 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.47%)413.0 V3.24 V (0.78%)214.6 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.38%)413.4 V2.57 V (0.62%)169.9 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.3%)413.8 V2.05 V (0.5%)135.9 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.24%)414.0 V1.67 V (0.4%)110.2 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.19%)414.2 V1.28 V (0.31%)84.9 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.15%)414.4 V1.03 V (0.25%)67.9 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.11%)414.5 V0.77 V (0.19%)51.0 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 63A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 63A over 80m at 415V (voltage drop: 11.68V or 2.81%).

What is the power capacity of 63A at 415V?

At unity power factor, 63A at 415V supports 45.28 kW with a standard 63A circuit breaker.