⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

80 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 9.49V (2.29%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 11.18V (2.69%)
Voltage at Load405.5 VLine Loss: 1314.8 W
Max Power & Breaker57.5 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A158.15 V (38.11%)256.9 V260.87 V (62.86%)21913.6 WDrop High
2.5 mm²24 A18 A94.89 V (22.86%)320.1 V156.52 V (37.72%)13148.2 WDrop High
4 mm²32 A25 A59.31 V (14.29%)355.7 V97.83 V (23.57%)8217.6 WDrop High
6 mm²41 A32 A39.54 V (9.53%)375.5 V65.22 V (15.72%)5478.4 WDrop High
10 mm²57 A44 A23.72 V (5.72%)391.3 V39.13 V (9.43%)3287.0 WDrop High
16 mm²76 A59 A14.83 V (3.57%)400.2 V24.46 V (5.89%)2054.4 WDrop High
25 mm²101 A78 A9.49 V (2.29%)405.5 V15.65 V (3.77%)1314.8 W✓ OK (≤3%)
35 mm²125 A97 A6.78 V (1.63%)408.2 V11.18 V (2.69%)939.2 W✓ OK (≤3%)
50 mm²151 A118 A4.74 V (1.14%)410.3 V7.83 V (1.89%)657.4 W✓ OK (≤3%)
70 mm²192 A150 A3.39 V (0.82%)411.6 V5.59 V (1.35%)469.6 W✓ OK (≤3%)
95 mm²232 A181 A2.5 V (0.6%)412.5 V4.12 V (0.99%)346.0 W✓ OK (≤3%)
120 mm²269 A210 A1.98 V (0.48%)413.0 V3.26 V (0.79%)273.9 W✓ OK (≤3%)
150 mm²309 A241 A1.58 V (0.38%)413.4 V2.61 V (0.63%)219.1 W✓ OK (≤3%)
185 mm²353 A275 A1.28 V (0.31%)413.7 V2.12 V (0.51%)177.7 W✓ OK (≤3%)
240 mm²415 A324 A0.99 V (0.24%)414.0 V1.63 V (0.39%)137.0 W✓ OK (≤3%)
300 mm²477 A372 A0.79 V (0.19%)414.2 V1.3 V (0.31%)109.6 W✓ OK (≤3%)
400 mm²570 A445 A0.59 V (0.14%)414.4 V0.98 V (0.24%)82.2 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 80A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 80m at 415V (voltage drop: 9.49V or 2.29%).

What is the power capacity of 80A at 415V?

At unity power factor, 80A at 415V supports 57.5 kW with a standard 80A circuit breaker.