175 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 1.18V (2.46%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.24V (2.57%)
Voltage at Load46.8 VLine Loss: 207.0 W
Max Power & Breaker8.4 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.9 V (156.04%)0.0 V123.55 V (257.4%)13107.5 WDrop High
2.5 mm²24 A18 A44.94 V (93.63%)3.1 V74.13 V (154.44%)7864.5 WDrop High
4 mm²32 A25 A28.09 V (58.52%)19.9 V46.33 V (96.52%)4915.3 WDrop High
6 mm²41 A32 A18.72 V (39.01%)29.3 V30.89 V (64.35%)3276.9 WDrop High
10 mm²57 A44 A11.24 V (23.41%)36.8 V18.53 V (38.61%)1966.1 WDrop High
16 mm²76 A59 A7.02 V (14.63%)41.0 V11.58 V (24.13%)1228.8 WDrop High
25 mm²101 A78 A4.49 V (9.36%)43.5 V7.41 V (15.44%)786.5 WDrop High
35 mm²125 A97 A3.21 V (6.69%)44.8 V5.29 V (11.03%)561.8 WDrop High
50 mm²151 A118 A2.25 V (4.68%)45.8 V3.71 V (7.72%)393.2 WDrop High
70 mm²192 A150 A1.6 V (3.34%)46.4 V2.65 V (5.52%)280.9 W~ ≤5%
95 mm²232 A181 A1.18 V (2.46%)46.8 V1.95 V (4.06%)207.0 W✓ OK (≤3%)
120 mm²269 A210 A0.94 V (1.95%)47.1 V1.54 V (3.22%)163.8 W✓ OK (≤3%)
150 mm²309 A241 A0.75 V (1.56%)47.3 V1.24 V (2.57%)131.1 W✓ OK (≤3%)
185 mm²353 A275 A0.61 V (1.27%)47.4 V1.0 V (2.09%)106.3 W✓ OK (≤3%)
240 mm²415 A324 A0.47 V (0.98%)47.5 V0.77 V (1.61%)81.9 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.78%)47.6 V0.62 V (1.29%)65.5 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.59%)47.7 V0.46 V (0.97%)49.2 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 175A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 175A over 15m at 48V (voltage drop: 1.18V or 2.46%).

What is the power capacity of 175A at 48V?

At unity power factor, 175A at 48V supports 8.4 kW with a standard 175A circuit breaker.