175 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.25V (2.6%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 1.34V (2.78%)
Voltage at Load46.8 VLine Loss: 218.5 W
Max Power & Breaker8.4 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A99.87 V (208.06%)0.0 V164.73 V (343.19%)17476.7 WDrop High
2.5 mm²24 A18 A59.92 V (124.83%)0.0 V98.84 V (205.92%)10486.0 WDrop High
4 mm²32 A25 A37.45 V (78.02%)10.6 V61.77 V (128.7%)6553.8 WDrop High
6 mm²41 A32 A24.97 V (52.01%)23.0 V41.18 V (85.8%)4369.2 WDrop High
10 mm²57 A44 A14.98 V (31.21%)33.0 V24.71 V (51.48%)2621.5 WDrop High
16 mm²76 A59 A9.36 V (19.51%)38.6 V15.44 V (32.17%)1638.4 WDrop High
25 mm²101 A78 A5.99 V (12.48%)42.0 V9.88 V (20.59%)1048.6 WDrop High
35 mm²125 A97 A4.28 V (8.92%)43.7 V7.06 V (14.71%)749.0 WDrop High
50 mm²151 A118 A3.0 V (6.24%)45.0 V4.94 V (10.3%)524.3 WDrop High
70 mm²192 A150 A2.14 V (4.46%)45.9 V3.53 V (7.35%)374.5 W~ ≤5%
95 mm²232 A181 A1.58 V (3.29%)46.4 V2.6 V (5.42%)275.9 W~ ≤5%
120 mm²269 A210 A1.25 V (2.6%)46.8 V2.06 V (4.29%)218.5 W✓ OK (≤3%)
150 mm²309 A241 A1.0 V (2.08%)47.0 V1.65 V (3.43%)174.8 W✓ OK (≤3%)
185 mm²353 A275 A0.81 V (1.69%)47.2 V1.34 V (2.78%)141.7 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (1.3%)47.4 V1.03 V (2.14%)109.2 W✓ OK (≤3%)
300 mm²477 A372 A0.5 V (1.04%)47.5 V0.82 V (1.72%)87.4 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.78%)47.6 V0.62 V (1.29%)65.5 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 175A at 20 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 175A over 20m at 48V (voltage drop: 1.25V or 2.6%).

What is the power capacity of 175A at 48V?

At unity power factor, 175A at 48V supports 8.4 kW with a standard 175A circuit breaker.