175 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 5.46V (2.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.41V (2.35%)
Voltage at Load224.5 VLine Loss: 955.8 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A873.83 V (379.93%)0.0 V1441.42 V (626.7%)152920.8 WDrop High
2.5 mm²24 A18 A524.3 V (227.96%)0.0 V864.85 V (376.02%)91752.5 WDrop High
4 mm²32 A25 A327.69 V (142.47%)0.0 V540.53 V (235.01%)57345.3 WDrop High
6 mm²41 A32 A218.46 V (94.98%)11.5 V360.35 V (156.68%)38230.2 WDrop High
10 mm²57 A44 A131.07 V (56.99%)98.9 V216.21 V (94.01%)22938.1 WDrop High
16 mm²76 A59 A81.92 V (35.62%)148.1 V135.13 V (58.75%)14336.3 WDrop High
25 mm²101 A78 A52.43 V (22.8%)177.6 V86.48 V (37.6%)9175.2 WDrop High
35 mm²125 A97 A37.45 V (16.28%)192.6 V61.77 V (26.86%)6553.7 WDrop High
50 mm²151 A118 A26.21 V (11.4%)203.8 V43.24 V (18.8%)4587.6 WDrop High
70 mm²192 A150 A18.72 V (8.14%)211.3 V30.89 V (13.43%)3276.9 WDrop High
95 mm²232 A181 A13.8 V (6.0%)216.2 V22.76 V (9.9%)2414.5 WDrop High
120 mm²269 A210 A10.92 V (4.75%)219.1 V18.02 V (7.83%)1911.5 W~ ≤5%
150 mm²309 A241 A8.74 V (3.8%)221.3 V14.41 V (6.27%)1529.2 W~ ≤5%
185 mm²353 A275 A7.09 V (3.08%)222.9 V11.69 V (5.08%)1239.9 W~ ≤5%
240 mm²415 A324 A5.46 V (2.37%)224.5 V9.01 V (3.92%)955.8 W✓ OK (≤3%)
300 mm²477 A372 A4.37 V (1.9%)225.6 V7.21 V (3.13%)764.6 W✓ OK (≤3%)
400 mm²570 A445 A3.28 V (1.42%)226.7 V5.41 V (2.35%)573.5 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 175A at 175 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 175A over 175m at 230V (voltage drop: 5.46V or 2.37%).

What is the power capacity of 175A at 230V?

At unity power factor, 175A at 230V supports 40.25 kW with a standard 175A circuit breaker.