⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

175 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 0.54V (2.23%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.65V (2.71%)
Voltage at Load23.5 VLine Loss: 93.6 W
Max Power & Breaker4.2 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.97 V (104.03%)0.0 V41.18 V (171.6%)4369.2 WDrop High
2.5 mm²24 A18 A14.98 V (62.42%)9.0 V24.71 V (102.96%)2621.5 WDrop High
4 mm²32 A25 A9.36 V (39.01%)14.6 V15.44 V (64.35%)1638.4 WDrop High
6 mm²41 A32 A6.24 V (26.01%)17.8 V10.3 V (42.9%)1092.3 WDrop High
10 mm²57 A44 A3.74 V (15.6%)20.3 V6.18 V (25.74%)655.4 WDrop High
16 mm²76 A59 A2.34 V (9.75%)21.7 V3.86 V (16.09%)409.6 WDrop High
25 mm²101 A78 A1.5 V (6.24%)22.5 V2.47 V (10.3%)262.1 WDrop High
35 mm²125 A97 A1.07 V (4.46%)22.9 V1.76 V (7.35%)187.2 WDrop High
50 mm²151 A118 A0.75 V (3.12%)23.3 V1.24 V (5.15%)131.1 WDrop High
70 mm²192 A150 A0.54 V (2.23%)23.5 V0.88 V (3.68%)93.6 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (1.64%)23.6 V0.65 V (2.71%)69.0 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (1.3%)23.7 V0.51 V (2.14%)54.6 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (1.04%)23.8 V0.41 V (1.72%)43.7 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.84%)23.8 V0.33 V (1.39%)35.4 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.65%)23.8 V0.26 V (1.07%)27.3 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.52%)23.9 V0.21 V (0.86%)21.8 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.39%)23.9 V0.15 V (0.64%)16.4 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 175A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 175A over 5m at 24V (voltage drop: 0.54V or 2.23%).

What is the power capacity of 175A at 24V?

At unity power factor, 175A at 24V supports 4.2 kW with a standard 175A circuit breaker.