175 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.62V (2.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.77V (3.22%)
Voltage at Load23.4 VLine Loss: 109.2 W
Max Power & Breaker4.2 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.83 V (520.14%)0.0 V205.92 V (857.99%)21845.8 WDrop High
2.5 mm²24 A18 A74.9 V (312.08%)0.0 V123.55 V (514.79%)13107.5 WDrop High
4 mm²32 A25 A46.81 V (195.05%)0.0 V77.22 V (321.74%)8192.2 WDrop High
6 mm²41 A32 A31.21 V (130.03%)0.0 V51.48 V (214.5%)5461.5 WDrop High
10 mm²57 A44 A18.72 V (78.02%)5.3 V30.89 V (128.7%)3276.9 WDrop High
16 mm²76 A59 A11.7 V (48.76%)12.3 V19.3 V (80.44%)2048.0 WDrop High
25 mm²101 A78 A7.49 V (31.21%)16.5 V12.35 V (51.48%)1310.7 WDrop High
35 mm²125 A97 A5.35 V (22.29%)18.7 V8.82 V (36.77%)936.2 WDrop High
50 mm²151 A118 A3.74 V (15.6%)20.3 V6.18 V (25.74%)655.4 WDrop High
70 mm²192 A150 A2.67 V (11.15%)21.3 V4.41 V (18.39%)468.1 WDrop High
95 mm²232 A181 A1.97 V (8.21%)22.0 V3.25 V (13.55%)344.9 WDrop High
120 mm²269 A210 A1.56 V (6.5%)22.4 V2.57 V (10.72%)273.1 WDrop High
150 mm²309 A241 A1.25 V (5.2%)22.8 V2.06 V (8.58%)218.5 WDrop High
185 mm²353 A275 A1.01 V (4.22%)23.0 V1.67 V (6.96%)177.1 W~ ≤5%
240 mm²415 A324 A0.78 V (3.25%)23.2 V1.29 V (5.36%)136.5 W~ ≤5%
300 mm²477 A372 A0.62 V (2.6%)23.4 V1.03 V (4.29%)109.2 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (1.95%)23.5 V0.77 V (3.22%)81.9 W✓ OK (≤3%)

FAQ — 175 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 175A at 25 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 175A over 25m at 24V (voltage drop: 0.62V or 2.6%).

What is the power capacity of 175A at 24V?

At unity power factor, 175A at 24V supports 4.2 kW with a standard 175A circuit breaker.