20 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 8.34V (2.01%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 9.17V (2.21%)
Voltage at Load406.7 VLine Loss: 288.9 W
Max Power & Breaker14.38 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.24 V (5.36%)392.8 V36.68 V (8.84%)770.4 WDrop High
2.5 mm²24 A18 A13.34 V (3.22%)401.7 V22.01 V (5.3%)462.2 W~ ≤5%
4 mm²32 A25 A8.34 V (2.01%)406.7 V13.76 V (3.31%)288.9 W✓ OK (≤3%)
6 mm²41 A32 A5.56 V (1.34%)409.4 V9.17 V (2.21%)192.6 W✓ OK (≤3%)
10 mm²57 A44 A3.34 V (0.8%)411.7 V5.5 V (1.33%)115.6 W✓ OK (≤3%)
16 mm²76 A59 A2.08 V (0.5%)412.9 V3.44 V (0.83%)72.2 W✓ OK (≤3%)
25 mm²101 A78 A1.33 V (0.32%)413.7 V2.2 V (0.53%)46.2 W✓ OK (≤3%)
35 mm²125 A97 A0.95 V (0.23%)414.0 V1.57 V (0.38%)33.0 W✓ OK (≤3%)
50 mm²151 A118 A0.67 V (0.16%)414.3 V1.1 V (0.27%)23.1 W✓ OK (≤3%)
70 mm²192 A150 A0.48 V (0.11%)414.5 V0.79 V (0.19%)16.5 W✓ OK (≤3%)
95 mm²232 A181 A0.35 V (0.08%)414.6 V0.58 V (0.14%)12.2 W✓ OK (≤3%)
120 mm²269 A210 A0.28 V (0.07%)414.7 V0.46 V (0.11%)9.6 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.05%)414.8 V0.37 V (0.09%)7.7 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.04%)414.8 V0.3 V (0.07%)6.2 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.03%)414.9 V0.23 V (0.06%)4.8 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.03%)414.9 V0.18 V (0.04%)3.9 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.02%)414.9 V0.14 V (0.03%)2.9 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 20A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 20A over 45m at 415V (voltage drop: 8.34V or 2.01%).

What is the power capacity of 20A at 415V?

At unity power factor, 20A at 415V supports 14.38 kW with a standard 20A circuit breaker.