63 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 6.57V (1.58%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.93V (1.67%)
Voltage at Load408.4 VLine Loss: 716.7 W
Max Power & Breaker45.28 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A70.05 V (16.88%)344.9 V115.56 V (27.85%)7644.3 WDrop High
2.5 mm²24 A18 A42.03 V (10.13%)373.0 V69.33 V (16.71%)4586.6 WDrop High
4 mm²32 A25 A26.27 V (6.33%)388.7 V43.33 V (10.44%)2866.6 WDrop High
6 mm²41 A32 A17.51 V (4.22%)397.5 V28.89 V (6.96%)1911.1 WDrop High
10 mm²57 A44 A10.51 V (2.53%)404.5 V17.33 V (4.18%)1146.6 WDrop High
16 mm²76 A59 A6.57 V (1.58%)408.4 V10.83 V (2.61%)716.7 W✓ OK (≤3%)
25 mm²101 A78 A4.2 V (1.01%)410.8 V6.93 V (1.67%)458.7 W✓ OK (≤3%)
35 mm²125 A97 A3.0 V (0.72%)412.0 V4.95 V (1.19%)327.6 W✓ OK (≤3%)
50 mm²151 A118 A2.1 V (0.51%)412.9 V3.47 V (0.84%)229.3 W✓ OK (≤3%)
70 mm²192 A150 A1.5 V (0.36%)413.5 V2.48 V (0.6%)163.8 W✓ OK (≤3%)
95 mm²232 A181 A1.11 V (0.27%)413.9 V1.82 V (0.44%)120.7 W✓ OK (≤3%)
120 mm²269 A210 A0.88 V (0.21%)414.1 V1.44 V (0.35%)95.6 W✓ OK (≤3%)
150 mm²309 A241 A0.7 V (0.17%)414.3 V1.16 V (0.28%)76.4 W✓ OK (≤3%)
185 mm²353 A275 A0.57 V (0.14%)414.4 V0.94 V (0.23%)62.0 W✓ OK (≤3%)
240 mm²415 A324 A0.44 V (0.11%)414.6 V0.72 V (0.17%)47.8 W✓ OK (≤3%)
300 mm²477 A372 A0.35 V (0.08%)414.6 V0.58 V (0.14%)38.2 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (0.06%)414.7 V0.43 V (0.1%)28.7 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 63A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 63A over 45m at 415V (voltage drop: 6.57V or 1.58%).

What is the power capacity of 63A at 415V?

At unity power factor, 63A at 415V supports 45.28 kW with a standard 63A circuit breaker.