25 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 10.42V (2.51%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 11.46V (2.76%)
Voltage at Load404.6 VLine Loss: 451.4 W
Max Power & Breaker17.97 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A27.8 V (6.7%)387.2 V45.86 V (11.05%)1203.8 WDrop High
2.5 mm²24 A18 A16.68 V (4.02%)398.3 V27.51 V (6.63%)722.2 WDrop High
4 mm²32 A25 A10.42 V (2.51%)404.6 V17.2 V (4.14%)451.4 W✓ OK (≤3%)
6 mm²41 A32 A6.95 V (1.67%)408.1 V11.46 V (2.76%)300.9 W✓ OK (≤3%)
10 mm²57 A44 A4.17 V (1.0%)410.8 V6.88 V (1.66%)180.6 W✓ OK (≤3%)
16 mm²76 A59 A2.61 V (0.63%)412.4 V4.3 V (1.04%)112.9 W✓ OK (≤3%)
25 mm²101 A78 A1.67 V (0.4%)413.3 V2.75 V (0.66%)72.2 W✓ OK (≤3%)
35 mm²125 A97 A1.19 V (0.29%)413.8 V1.97 V (0.47%)51.6 W✓ OK (≤3%)
50 mm²151 A118 A0.83 V (0.2%)414.2 V1.38 V (0.33%)36.1 W✓ OK (≤3%)
70 mm²192 A150 A0.6 V (0.14%)414.4 V0.98 V (0.24%)25.8 W✓ OK (≤3%)
95 mm²232 A181 A0.44 V (0.11%)414.6 V0.72 V (0.17%)19.0 W✓ OK (≤3%)
120 mm²269 A210 A0.35 V (0.08%)414.7 V0.57 V (0.14%)15.0 W✓ OK (≤3%)
150 mm²309 A241 A0.28 V (0.07%)414.7 V0.46 V (0.11%)12.0 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.05%)414.8 V0.37 V (0.09%)9.8 W✓ OK (≤3%)
240 mm²415 A324 A0.17 V (0.04%)414.8 V0.29 V (0.07%)7.5 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.03%)414.9 V0.23 V (0.06%)6.0 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.03%)414.9 V0.17 V (0.04%)4.5 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 25A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 25A over 45m at 415V (voltage drop: 10.42V or 2.51%).

What is the power capacity of 25A at 415V?

At unity power factor, 25A at 415V supports 17.97 kW with a standard 25A circuit breaker.