20 Amp Cable Size at 70 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.63V (2.63%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.66V (2.75%)
Voltage at Load23.4 VLine Loss: 12.6 W
Max Power & Breaker0.48 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A39.95 V (166.44%)0.0 V65.89 V (274.56%)798.9 WDrop High
2.5 mm²24 A18 A23.97 V (99.87%)0.0 V39.54 V (164.73%)479.4 WDrop High
4 mm²32 A25 A14.98 V (62.42%)9.0 V24.71 V (102.96%)299.6 WDrop High
6 mm²41 A32 A9.99 V (41.61%)14.0 V16.47 V (68.64%)199.7 WDrop High
10 mm²57 A44 A5.99 V (24.97%)18.0 V9.88 V (41.18%)119.8 WDrop High
16 mm²76 A59 A3.75 V (15.6%)20.3 V6.18 V (25.74%)74.9 WDrop High
25 mm²101 A78 A2.4 V (9.99%)21.6 V3.95 V (16.47%)47.9 WDrop High
35 mm²125 A97 A1.71 V (7.13%)22.3 V2.82 V (11.77%)34.2 WDrop High
50 mm²151 A118 A1.2 V (4.99%)22.8 V1.98 V (8.24%)24.0 W~ ≤5%
70 mm²192 A150 A0.86 V (3.57%)23.1 V1.41 V (5.88%)17.1 W~ ≤5%
95 mm²232 A181 A0.63 V (2.63%)23.4 V1.04 V (4.34%)12.6 W✓ OK (≤3%)
120 mm²269 A210 A0.5 V (2.08%)23.5 V0.82 V (3.43%)10.0 W✓ OK (≤3%)
150 mm²309 A241 A0.4 V (1.66%)23.6 V0.66 V (2.75%)8.0 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (1.35%)23.7 V0.53 V (2.23%)6.5 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (1.04%)23.8 V0.41 V (1.72%)5.0 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.83%)23.8 V0.33 V (1.37%)4.0 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.62%)23.9 V0.25 V (1.03%)3.0 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 70 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 20A at 70 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 20A over 70m at 24V (voltage drop: 0.63V or 2.63%).

What is the power capacity of 20A at 24V?

At unity power factor, 20A at 24V supports 0.48 kW with a standard 20A circuit breaker.