20 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 0.54V (2.23%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.56V (2.35%)
Voltage at Load23.5 VLine Loss: 10.7 W
Max Power & Breaker0.48 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.71 V (23.78%)18.3 V9.41 V (39.22%)114.1 WDrop High
2.5 mm²24 A18 A3.42 V (14.27%)20.6 V5.65 V (23.53%)68.5 WDrop High
4 mm²32 A25 A2.14 V (8.92%)21.9 V3.53 V (14.71%)42.8 WDrop High
6 mm²41 A32 A1.43 V (5.94%)22.6 V2.35 V (9.81%)28.5 WDrop High
10 mm²57 A44 A0.86 V (3.57%)23.1 V1.41 V (5.88%)17.1 W~ ≤5%
16 mm²76 A59 A0.54 V (2.23%)23.5 V0.88 V (3.68%)10.7 W✓ OK (≤3%)
25 mm²101 A78 A0.34 V (1.43%)23.7 V0.56 V (2.35%)6.8 W✓ OK (≤3%)
35 mm²125 A97 A0.24 V (1.02%)23.8 V0.4 V (1.68%)4.9 W✓ OK (≤3%)
50 mm²151 A118 A0.17 V (0.71%)23.8 V0.28 V (1.18%)3.4 W✓ OK (≤3%)
70 mm²192 A150 A0.12 V (0.51%)23.9 V0.2 V (0.84%)2.4 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.38%)23.9 V0.15 V (0.62%)1.8 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.3%)23.9 V0.12 V (0.49%)1.4 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.24%)23.9 V0.09 V (0.39%)1.1 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.19%)24.0 V0.08 V (0.32%)0.9 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.15%)24.0 V0.06 V (0.25%)0.7 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.12%)24.0 V0.05 V (0.2%)0.6 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.09%)24.0 V0.04 V (0.15%)0.4 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 20A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 20A over 10m at 24V (voltage drop: 0.54V or 2.23%).

What is the power capacity of 20A at 24V?

At unity power factor, 20A at 24V supports 0.48 kW with a standard 20A circuit breaker.