200 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 12.36V (2.98%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 10.19V (2.46%)
Voltage at Load402.6 VLine Loss: 4280.0 W
Max Power & Breaker143.76 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1235.53 V (297.72%)0.0 V2038.05 V (491.1%)428000.0 WDrop High
2.5 mm²24 A18 A741.32 V (178.63%)0.0 V1222.83 V (294.66%)256800.0 WDrop High
4 mm²32 A25 A463.32 V (111.64%)0.0 V764.27 V (184.16%)160500.0 WDrop High
6 mm²41 A32 A308.88 V (74.43%)106.1 V509.51 V (122.77%)107000.0 WDrop High
10 mm²57 A44 A185.33 V (44.66%)229.7 V305.71 V (73.66%)64200.0 WDrop High
16 mm²76 A59 A115.83 V (27.91%)299.2 V191.07 V (46.04%)40125.0 WDrop High
25 mm²101 A78 A74.13 V (17.86%)340.9 V122.28 V (29.47%)25680.0 WDrop High
35 mm²125 A97 A52.95 V (12.76%)362.0 V87.34 V (21.05%)18342.9 WDrop High
50 mm²151 A118 A37.07 V (8.93%)377.9 V61.14 V (14.73%)12840.0 WDrop High
70 mm²192 A150 A26.48 V (6.38%)388.5 V43.67 V (10.52%)9171.4 WDrop High
95 mm²232 A181 A19.51 V (4.7%)395.5 V32.18 V (7.75%)6757.9 W~ ≤5%
120 mm²269 A210 A15.44 V (3.72%)399.6 V25.48 V (6.14%)5350.0 W~ ≤5%
150 mm²309 A241 A12.36 V (2.98%)402.6 V20.38 V (4.91%)4280.0 W✓ OK (≤3%)
185 mm²353 A275 A10.02 V (2.41%)405.0 V16.52 V (3.98%)3470.3 W✓ OK (≤3%)
240 mm²415 A324 A7.72 V (1.86%)407.3 V12.74 V (3.07%)2675.0 W✓ OK (≤3%)
300 mm²477 A372 A6.18 V (1.49%)408.8 V10.19 V (2.46%)2140.0 W✓ OK (≤3%)
400 mm²570 A445 A4.63 V (1.12%)410.4 V7.64 V (1.84%)1605.0 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 200A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 200A over 250m at 415V (voltage drop: 12.36V or 2.98%).

What is the power capacity of 200A at 415V?

At unity power factor, 200A at 415V supports 143.76 kW with a standard 200A circuit breaker.