125 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 12.19V (2.94%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.33V (2.49%)
Voltage at Load402.8 VLine Loss: 2639.8 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A772.21 V (186.07%)0.0 V1273.78 V (306.93%)167187.5 WDrop High
2.5 mm²24 A18 A463.32 V (111.64%)0.0 V764.27 V (184.16%)100312.5 WDrop High
4 mm²32 A25 A289.58 V (69.78%)125.4 V477.67 V (115.1%)62695.3 WDrop High
6 mm²41 A32 A193.05 V (46.52%)221.9 V318.44 V (76.73%)41796.9 WDrop High
10 mm²57 A44 A115.83 V (27.91%)299.2 V191.07 V (46.04%)25078.1 WDrop High
16 mm²76 A59 A72.39 V (17.44%)342.6 V119.42 V (28.78%)15673.8 WDrop High
25 mm²101 A78 A46.33 V (11.16%)368.7 V76.43 V (18.42%)10031.2 WDrop High
35 mm²125 A97 A33.09 V (7.97%)381.9 V54.59 V (13.15%)7165.2 WDrop High
50 mm²151 A118 A23.17 V (5.58%)391.8 V38.21 V (9.21%)5015.6 WDrop High
70 mm²192 A150 A16.55 V (3.99%)398.5 V27.3 V (6.58%)3582.6 W~ ≤5%
95 mm²232 A181 A12.19 V (2.94%)402.8 V20.11 V (4.85%)2639.8 W✓ OK (≤3%)
120 mm²269 A210 A9.65 V (2.33%)405.3 V15.92 V (3.84%)2089.8 W✓ OK (≤3%)
150 mm²309 A241 A7.72 V (1.86%)407.3 V12.74 V (3.07%)1671.9 W✓ OK (≤3%)
185 mm²353 A275 A6.26 V (1.51%)408.7 V10.33 V (2.49%)1355.6 W✓ OK (≤3%)
240 mm²415 A324 A4.83 V (1.16%)410.2 V7.96 V (1.92%)1044.9 W✓ OK (≤3%)
300 mm²477 A372 A3.86 V (0.93%)411.1 V6.37 V (1.53%)835.9 W✓ OK (≤3%)
400 mm²570 A445 A2.9 V (0.7%)412.1 V4.78 V (1.15%)627.0 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 125A over 250m at 415V (voltage drop: 12.19V or 2.94%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.