225 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.4V (2.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.95V (14.48%)
Voltage at Load46.6 VLine Loss: 316.0 W
Max Power & Breaker10.8 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1123.5 V (2340.62%)0.0 V1853.25 V (3860.94%)252787.5 WDrop High
2.5 mm²24 A18 A674.1 V (1404.37%)0.0 V1111.95 V (2316.56%)151672.5 WDrop High
4 mm²32 A25 A421.31 V (877.73%)0.0 V694.97 V (1447.85%)94795.3 WDrop High
6 mm²41 A32 A280.88 V (585.16%)0.0 V463.31 V (965.23%)63196.9 WDrop High
10 mm²57 A44 A168.52 V (351.09%)0.0 V277.99 V (579.14%)37918.1 WDrop High
16 mm²76 A59 A105.33 V (219.43%)0.0 V173.74 V (361.96%)23698.8 WDrop High
25 mm²101 A78 A67.41 V (140.44%)0.0 V111.19 V (231.66%)15167.2 WDrop High
35 mm²125 A97 A48.15 V (100.31%)0.0 V79.42 V (165.47%)10833.7 WDrop High
50 mm²151 A118 A33.7 V (70.22%)14.3 V55.6 V (115.83%)7583.6 WDrop High
70 mm²192 A150 A24.07 V (50.16%)23.9 V39.71 V (82.73%)5416.9 WDrop High
95 mm²232 A181 A17.74 V (36.96%)30.3 V29.26 V (60.96%)3991.4 WDrop High
120 mm²269 A210 A14.04 V (29.26%)34.0 V23.17 V (48.26%)3159.8 WDrop High
150 mm²309 A241 A11.23 V (23.41%)36.8 V18.53 V (38.61%)2527.9 WDrop High
185 mm²353 A275 A9.11 V (18.98%)38.9 V15.03 V (31.3%)2049.6 WDrop High
240 mm²415 A324 A7.02 V (14.63%)41.0 V11.58 V (24.13%)1579.9 WDrop High
300 mm²477 A372 A5.62 V (11.7%)42.4 V9.27 V (19.3%)1263.9 WDrop High
400 mm²570 A445 A4.21 V (8.78%)43.8 V6.95 V (14.48%)948.0 WDrop High

FAQ — 225 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 225A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 225A over 175m at 48V (voltage drop: 1.4V or 2.93%).

What is the power capacity of 225A at 48V?

At unity power factor, 225A at 48V supports 10.8 kW with a standard 225A circuit breaker.