125 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.17V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.86V (8.04%)
Voltage at Load46.8 VLine Loss: 146.3 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A624.17 V (1300.35%)0.0 V1029.58 V (2144.97%)78020.8 WDrop High
2.5 mm²24 A18 A374.5 V (780.21%)0.0 V617.75 V (1286.98%)46812.5 WDrop High
4 mm²32 A25 A234.06 V (487.63%)0.0 V386.09 V (804.36%)29257.8 WDrop High
6 mm²41 A32 A156.04 V (325.09%)0.0 V257.4 V (536.24%)19505.2 WDrop High
10 mm²57 A44 A93.62 V (195.05%)0.0 V154.44 V (321.74%)11703.1 WDrop High
16 mm²76 A59 A58.52 V (121.91%)0.0 V96.52 V (201.09%)7314.5 WDrop High
25 mm²101 A78 A37.45 V (78.02%)10.6 V61.77 V (128.7%)4681.2 WDrop High
35 mm²125 A97 A26.75 V (55.73%)21.3 V44.12 V (91.93%)3343.7 WDrop High
50 mm²151 A118 A18.72 V (39.01%)29.3 V30.89 V (64.35%)2340.6 WDrop High
70 mm²192 A150 A13.37 V (27.86%)34.6 V22.06 V (45.96%)1671.9 WDrop High
95 mm²232 A181 A9.86 V (20.53%)38.1 V16.26 V (33.87%)1231.9 WDrop High
120 mm²269 A210 A7.8 V (16.25%)40.2 V12.87 V (26.81%)975.3 WDrop High
150 mm²309 A241 A6.24 V (13.0%)41.8 V10.3 V (21.45%)780.2 WDrop High
185 mm²353 A275 A5.06 V (10.54%)42.9 V8.35 V (17.39%)632.6 WDrop High
240 mm²415 A324 A3.9 V (8.13%)44.1 V6.43 V (13.41%)487.6 WDrop High
300 mm²477 A372 A3.12 V (6.5%)44.9 V5.15 V (10.72%)390.1 WDrop High
400 mm²570 A445 A2.34 V (4.88%)45.7 V3.86 V (8.04%)292.6 W~ ≤5%

FAQ — 125 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 125A over 175m at 48V (voltage drop: 1.17V or 2.44%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.