225 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 2.19V (0.53%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 2.29V (0.55%)
Voltage at Load412.8 VLine Loss: 855.3 W
Max Power & Breaker161.73 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A139.0 V (33.49%)276.0 V229.28 V (55.25%)54168.7 WDrop High
2.5 mm²24 A18 A83.4 V (20.1%)331.6 V137.57 V (33.15%)32501.2 WDrop High
4 mm²32 A25 A52.12 V (12.56%)362.9 V85.98 V (20.72%)20313.3 WDrop High
6 mm²41 A32 A34.75 V (8.37%)380.3 V57.32 V (13.81%)13542.2 WDrop High
10 mm²57 A44 A20.85 V (5.02%)394.2 V34.39 V (8.29%)8125.3 WDrop High
16 mm²76 A59 A13.03 V (3.14%)402.0 V21.5 V (5.18%)5078.3 WDrop High
25 mm²101 A78 A8.34 V (2.01%)406.7 V13.76 V (3.31%)3250.1 WDrop High
35 mm²125 A97 A5.96 V (1.44%)409.0 V9.83 V (2.37%)2321.5 WDrop High
50 mm²151 A118 A4.17 V (1.0%)410.8 V6.88 V (1.66%)1625.1 WDrop High
70 mm²192 A150 A2.98 V (0.72%)412.0 V4.91 V (1.18%)1160.8 WDrop High
95 mm²232 A181 A2.19 V (0.53%)412.8 V3.62 V (0.87%)855.3 W✓ OK (≤3%)
120 mm²269 A210 A1.74 V (0.42%)413.3 V2.87 V (0.69%)677.1 W✓ OK (≤3%)
150 mm²309 A241 A1.39 V (0.33%)413.6 V2.29 V (0.55%)541.7 W✓ OK (≤3%)
185 mm²353 A275 A1.13 V (0.27%)413.9 V1.86 V (0.45%)439.2 W✓ OK (≤3%)
240 mm²415 A324 A0.87 V (0.21%)414.1 V1.43 V (0.35%)338.6 W✓ OK (≤3%)
300 mm²477 A372 A0.69 V (0.17%)414.3 V1.15 V (0.28%)270.8 W✓ OK (≤3%)
400 mm²570 A445 A0.52 V (0.13%)414.5 V0.86 V (0.21%)203.1 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 225A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 25m at 415V (voltage drop: 2.19V or 0.53%).

What is the power capacity of 225A at 415V?

At unity power factor, 225A at 415V supports 161.73 kW with a standard 225A circuit breaker.