225 Amp Cable Size at 600 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)11× 400 mm²Drop: 1.31V (2.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 23.83V (49.64%)
Voltage at Load46.7 VLine Loss: 295.5 W
Max Power & Breaker10.8 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3852.0 V (8025.0%)0.0 V6354.0 V (13237.5%)866700.0 WDrop High
2.5 mm²24 A18 A2311.2 V (4815.0%)0.0 V3812.4 V (7942.5%)520020.0 WDrop High
4 mm²32 A25 A1444.5 V (3009.38%)0.0 V2382.75 V (4964.06%)325012.5 WDrop High
6 mm²41 A32 A963.0 V (2006.25%)0.0 V1588.5 V (3309.38%)216675.0 WDrop High
10 mm²57 A44 A577.8 V (1203.75%)0.0 V953.1 V (1985.62%)130005.0 WDrop High
16 mm²76 A59 A361.12 V (752.34%)0.0 V595.69 V (1241.02%)81253.1 WDrop High
25 mm²101 A78 A231.12 V (481.5%)0.0 V381.24 V (794.25%)52002.0 WDrop High
35 mm²125 A97 A165.09 V (343.93%)0.0 V272.31 V (567.32%)37144.3 WDrop High
50 mm²151 A118 A115.56 V (240.75%)0.0 V190.62 V (397.12%)26001.0 WDrop High
70 mm²192 A150 A82.54 V (171.96%)0.0 V136.16 V (283.66%)18572.1 WDrop High
95 mm²232 A181 A60.82 V (126.71%)0.0 V100.33 V (209.01%)13684.7 WDrop High
120 mm²269 A210 A48.15 V (100.31%)0.0 V79.42 V (165.47%)10833.8 WDrop High
150 mm²309 A241 A38.52 V (80.25%)9.5 V63.54 V (132.38%)8667.0 WDrop High
185 mm²353 A275 A31.23 V (65.07%)16.8 V51.52 V (107.33%)7027.3 WDrop High
240 mm²415 A324 A24.07 V (50.16%)23.9 V39.71 V (82.73%)5416.9 WDrop High
300 mm²477 A372 A19.26 V (40.12%)28.7 V31.77 V (66.19%)4333.5 WDrop High
400 mm²570 A445 A14.44 V (30.09%)33.6 V23.83 V (49.64%)3250.1 WDrop High

FAQ — 225 Amp Cable Size at 600 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 225A at 600 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 11× 400 mm² copper cable for 225A over 600m at 48V (voltage drop: 1.31V or 2.74%).

What is the power capacity of 225A at 48V?

At unity power factor, 225A at 48V supports 10.8 kW with a standard 225A circuit breaker.