250 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.16V (0.28%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 1.24V (0.3%)
Voltage at Load413.8 VLine Loss: 501.6 W
Max Power & Breaker179.7 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (22.33%)322.3 V152.85 V (36.83%)40125.0 WDrop High
2.5 mm²24 A18 A55.6 V (13.4%)359.4 V91.71 V (22.1%)24075.0 WDrop High
4 mm²32 A25 A34.75 V (8.37%)380.3 V57.32 V (13.81%)15046.9 WDrop High
6 mm²41 A32 A23.17 V (5.58%)391.8 V38.21 V (9.21%)10031.2 WDrop High
10 mm²57 A44 A13.9 V (3.35%)401.1 V22.93 V (5.52%)6018.8 WDrop High
16 mm²76 A59 A8.69 V (2.09%)406.3 V14.33 V (3.45%)3761.7 WDrop High
25 mm²101 A78 A5.56 V (1.34%)409.4 V9.17 V (2.21%)2407.5 WDrop High
35 mm²125 A97 A3.97 V (0.96%)411.0 V6.55 V (1.58%)1719.6 WDrop High
50 mm²151 A118 A2.78 V (0.67%)412.2 V4.59 V (1.1%)1203.8 WDrop High
70 mm²192 A150 A1.99 V (0.48%)413.0 V3.28 V (0.79%)859.8 WDrop High
95 mm²232 A181 A1.46 V (0.35%)413.5 V2.41 V (0.58%)633.6 WDrop High
120 mm²269 A210 A1.16 V (0.28%)413.8 V1.91 V (0.46%)501.6 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.22%)414.1 V1.53 V (0.37%)401.2 W✓ OK (≤3%)
185 mm²353 A275 A0.75 V (0.18%)414.2 V1.24 V (0.3%)325.3 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.14%)414.4 V0.96 V (0.23%)250.8 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.11%)414.5 V0.76 V (0.18%)200.6 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.08%)414.7 V0.57 V (0.14%)150.5 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 250A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 15m at 415V (voltage drop: 1.16V or 0.28%).

What is the power capacity of 250A at 415V?

At unity power factor, 250A at 415V supports 179.7 kW with a standard 250A circuit breaker.