⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

250 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.55V (2.39%)
Voltage at Load388.4 VLine Loss: 5015.6 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)401250.0 WDrop High
2.5 mm²24 A18 A555.99 V (139.0%)0.0 V917.12 V (229.28%)240750.0 WDrop High
4 mm²32 A25 A347.49 V (86.87%)52.5 V573.2 V (143.3%)150468.8 WDrop High
6 mm²41 A32 A231.66 V (57.92%)168.3 V382.13 V (95.53%)100312.5 WDrop High
10 mm²57 A44 A139.0 V (34.75%)261.0 V229.28 V (57.32%)60187.5 WDrop High
16 mm²76 A59 A86.87 V (21.72%)313.1 V143.3 V (35.83%)37617.2 WDrop High
25 mm²101 A78 A55.6 V (13.9%)344.4 V91.71 V (22.93%)24075.0 WDrop High
35 mm²125 A97 A39.71 V (9.93%)360.3 V65.51 V (16.38%)17196.4 WDrop High
50 mm²151 A118 A27.8 V (6.95%)372.2 V45.86 V (11.46%)12037.5 WDrop High
70 mm²192 A150 A19.86 V (4.96%)380.1 V32.75 V (8.19%)8598.2 WDrop High
95 mm²232 A181 A14.63 V (3.66%)385.4 V24.13 V (6.03%)6335.5 WDrop High
120 mm²269 A210 A11.58 V (2.9%)388.4 V19.11 V (4.78%)5015.6 W✓ OK (≤3%)
150 mm²309 A241 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4012.5 W✓ OK (≤3%)
185 mm²353 A275 A7.51 V (1.88%)392.5 V12.39 V (3.1%)3253.4 W✓ OK (≤3%)
240 mm²415 A324 A5.79 V (1.45%)394.2 V9.55 V (2.39%)2507.8 W✓ OK (≤3%)
300 mm²477 A372 A4.63 V (1.16%)395.4 V7.64 V (1.91%)2006.2 W✓ OK (≤3%)
400 mm²570 A445 A3.47 V (0.87%)396.5 V5.73 V (1.43%)1504.7 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 250A at 150 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 150m at 400V (voltage drop: 11.58V or 2.9%).

What is the power capacity of 250A at 400V?

At unity power factor, 250A at 400V supports 173.21 kW with a standard 250A circuit breaker.