⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

250 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.03V (22.98%)
Voltage at Load46.7 VLine Loss: 334.4 W
Max Power & Breaker12.0 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1783.33 V (3715.28%)0.0 V2941.67 V (6128.47%)445833.3 WDrop High
2.5 mm²24 A18 A1070.0 V (2229.17%)0.0 V1765.0 V (3677.08%)267500.0 WDrop High
4 mm²32 A25 A668.75 V (1393.23%)0.0 V1103.12 V (2298.18%)167187.5 WDrop High
6 mm²41 A32 A445.83 V (928.82%)0.0 V735.42 V (1532.12%)111458.3 WDrop High
10 mm²57 A44 A267.5 V (557.29%)0.0 V441.25 V (919.27%)66875.0 WDrop High
16 mm²76 A59 A167.19 V (348.31%)0.0 V275.78 V (574.54%)41796.9 WDrop High
25 mm²101 A78 A107.0 V (222.92%)0.0 V176.5 V (367.71%)26750.0 WDrop High
35 mm²125 A97 A76.43 V (159.23%)0.0 V126.07 V (262.65%)19107.1 WDrop High
50 mm²151 A118 A53.5 V (111.46%)0.0 V88.25 V (183.85%)13375.0 WDrop High
70 mm²192 A150 A38.21 V (79.61%)9.8 V63.04 V (131.32%)9553.6 WDrop High
95 mm²232 A181 A28.16 V (58.66%)19.8 V46.45 V (96.77%)7039.5 WDrop High
120 mm²269 A210 A22.29 V (46.44%)25.7 V36.77 V (76.61%)5572.9 WDrop High
150 mm²309 A241 A17.83 V (37.15%)30.2 V29.42 V (61.28%)4458.3 WDrop High
185 mm²353 A275 A14.46 V (30.12%)33.5 V23.85 V (49.69%)3614.9 WDrop High
240 mm²415 A324 A11.15 V (23.22%)36.9 V18.39 V (38.3%)2786.5 WDrop High
300 mm²477 A372 A8.92 V (18.58%)39.1 V14.71 V (30.64%)2229.2 WDrop High
400 mm²570 A445 A6.69 V (13.93%)41.3 V11.03 V (22.98%)1671.9 WDrop High

FAQ — 250 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 250A at 250 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 250A over 250m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 250A at 48V?

At unity power factor, 250A at 48V supports 12.0 kW with a standard 250A circuit breaker.