⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.11V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.1V (2.3%)
Voltage at Load46.9 VLine Loss: 27.9 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A178.33 V (371.53%)0.0 V294.17 V (612.85%)4458.3 WDrop High
2.5 mm²24 A18 A107.0 V (222.92%)0.0 V176.5 V (367.71%)2675.0 WDrop High
4 mm²32 A25 A66.88 V (139.32%)0.0 V110.31 V (229.82%)1671.9 WDrop High
6 mm²41 A32 A44.58 V (92.88%)3.4 V73.54 V (153.21%)1114.6 WDrop High
10 mm²57 A44 A26.75 V (55.73%)21.3 V44.12 V (91.93%)668.7 WDrop High
16 mm²76 A59 A16.72 V (34.83%)31.3 V27.58 V (57.45%)418.0 WDrop High
25 mm²101 A78 A10.7 V (22.29%)37.3 V17.65 V (36.77%)267.5 WDrop High
35 mm²125 A97 A7.64 V (15.92%)40.4 V12.61 V (26.26%)191.1 WDrop High
50 mm²151 A118 A5.35 V (11.15%)42.6 V8.82 V (18.39%)133.8 WDrop High
70 mm²192 A150 A3.82 V (7.96%)44.2 V6.3 V (13.13%)95.5 WDrop High
95 mm²232 A181 A2.82 V (5.87%)45.2 V4.64 V (9.68%)70.4 WDrop High
120 mm²269 A210 A2.23 V (4.64%)45.8 V3.68 V (7.66%)55.7 W~ ≤5%
150 mm²309 A241 A1.78 V (3.72%)46.2 V2.94 V (6.13%)44.6 W~ ≤5%
185 mm²353 A275 A1.45 V (3.01%)46.6 V2.39 V (4.97%)36.1 W~ ≤5%
240 mm²415 A324 A1.11 V (2.32%)46.9 V1.84 V (3.83%)27.9 W✓ OK (≤3%)
300 mm²477 A372 A0.89 V (1.86%)47.1 V1.47 V (3.06%)22.3 W✓ OK (≤3%)
400 mm²570 A445 A0.67 V (1.39%)47.3 V1.1 V (2.3%)16.7 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 250 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 25A over 250m at 48V (voltage drop: 1.11V or 2.32%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.