125 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.11V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.52V (11.49%)
Voltage at Load46.9 VLine Loss: 139.3 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A891.67 V (1857.64%)0.0 V1470.83 V (3064.24%)111458.3 WDrop High
2.5 mm²24 A18 A535.0 V (1114.58%)0.0 V882.5 V (1838.54%)66875.0 WDrop High
4 mm²32 A25 A334.38 V (696.61%)0.0 V551.56 V (1149.09%)41796.9 WDrop High
6 mm²41 A32 A222.92 V (464.41%)0.0 V367.71 V (766.06%)27864.6 WDrop High
10 mm²57 A44 A133.75 V (278.65%)0.0 V220.62 V (459.64%)16718.7 WDrop High
16 mm²76 A59 A83.59 V (174.15%)0.0 V137.89 V (287.27%)10449.2 WDrop High
25 mm²101 A78 A53.5 V (111.46%)0.0 V88.25 V (183.85%)6687.5 WDrop High
35 mm²125 A97 A38.21 V (79.61%)9.8 V63.04 V (131.32%)4776.8 WDrop High
50 mm²151 A118 A26.75 V (55.73%)21.2 V44.12 V (91.93%)3343.8 WDrop High
70 mm²192 A150 A19.11 V (39.81%)28.9 V31.52 V (65.66%)2388.4 WDrop High
95 mm²232 A181 A14.08 V (29.33%)33.9 V23.22 V (48.38%)1759.9 WDrop High
120 mm²269 A210 A11.15 V (23.22%)36.9 V18.39 V (38.3%)1393.2 WDrop High
150 mm²309 A241 A8.92 V (18.58%)39.1 V14.71 V (30.64%)1114.6 WDrop High
185 mm²353 A275 A7.23 V (15.06%)40.8 V11.93 V (24.85%)903.7 WDrop High
240 mm²415 A324 A5.57 V (11.61%)42.4 V9.19 V (19.15%)696.6 WDrop High
300 mm²477 A372 A4.46 V (9.29%)43.5 V7.35 V (15.32%)557.3 WDrop High
400 mm²570 A445 A3.34 V (6.97%)44.7 V5.52 V (11.49%)418.0 WDrop High

FAQ — 125 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 250 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 125A over 250m at 48V (voltage drop: 1.11V or 2.32%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.