250 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 0.45V (0.19%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.48V (0.21%)
Voltage at Load229.6 VLine Loss: 111.5 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.67 V (15.51%)194.3 V58.83 V (25.58%)8916.7 WDrop High
2.5 mm²24 A18 A21.4 V (9.3%)208.6 V35.3 V (15.35%)5350.0 WDrop High
4 mm²32 A25 A13.38 V (5.82%)216.6 V22.06 V (9.59%)3343.8 WDrop High
6 mm²41 A32 A8.92 V (3.88%)221.1 V14.71 V (6.39%)2229.2 WDrop High
10 mm²57 A44 A5.35 V (2.33%)224.7 V8.82 V (3.84%)1337.5 WDrop High
16 mm²76 A59 A3.34 V (1.45%)226.7 V5.52 V (2.4%)835.9 WDrop High
25 mm²101 A78 A2.14 V (0.93%)227.9 V3.53 V (1.53%)535.0 WDrop High
35 mm²125 A97 A1.53 V (0.66%)228.5 V2.52 V (1.1%)382.1 WDrop High
50 mm²151 A118 A1.07 V (0.47%)228.9 V1.76 V (0.77%)267.5 WDrop High
70 mm²192 A150 A0.76 V (0.33%)229.2 V1.26 V (0.55%)191.1 WDrop High
95 mm²232 A181 A0.56 V (0.24%)229.4 V0.93 V (0.4%)140.8 WDrop High
120 mm²269 A210 A0.45 V (0.19%)229.6 V0.74 V (0.32%)111.5 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (0.16%)229.6 V0.59 V (0.26%)89.2 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (0.13%)229.7 V0.48 V (0.21%)72.3 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.1%)229.8 V0.37 V (0.16%)55.7 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.08%)229.8 V0.29 V (0.13%)44.6 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.06%)229.9 V0.22 V (0.1%)33.4 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 250A at 5 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 5m at 230V (voltage drop: 0.45V or 0.19%).

What is the power capacity of 250A at 230V?

At unity power factor, 250A at 230V supports 57.5 kW with a standard 250A circuit breaker.