30 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.29V (2.3%)
Voltage at Load223.6 VLine Loss: 192.6 W
Max Power & Breaker6.9 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A149.8 V (65.13%)80.2 V247.1 V (107.43%)4494.0 WDrop High
2.5 mm²24 A18 A89.88 V (39.08%)140.1 V148.26 V (64.46%)2696.4 WDrop High
4 mm²32 A25 A56.17 V (24.42%)173.8 V92.66 V (40.29%)1685.2 WDrop High
6 mm²41 A32 A37.45 V (16.28%)192.6 V61.77 V (26.86%)1123.5 WDrop High
10 mm²57 A44 A22.47 V (9.77%)207.5 V37.06 V (16.12%)674.1 WDrop High
16 mm²76 A59 A14.04 V (6.11%)216.0 V23.17 V (10.07%)421.3 WDrop High
25 mm²101 A78 A8.99 V (3.91%)221.0 V14.83 V (6.45%)269.6 W~ ≤5%
35 mm²125 A97 A6.42 V (2.79%)223.6 V10.59 V (4.6%)192.6 W✓ OK (≤3%)
50 mm²151 A118 A4.49 V (1.95%)225.5 V7.41 V (3.22%)134.8 W✓ OK (≤3%)
70 mm²192 A150 A3.21 V (1.4%)226.8 V5.29 V (2.3%)96.3 W✓ OK (≤3%)
95 mm²232 A181 A2.37 V (1.03%)227.6 V3.9 V (1.7%)71.0 W✓ OK (≤3%)
120 mm²269 A210 A1.87 V (0.81%)228.1 V3.09 V (1.34%)56.2 W✓ OK (≤3%)
150 mm²309 A241 A1.5 V (0.65%)228.5 V2.47 V (1.07%)44.9 W✓ OK (≤3%)
185 mm²353 A275 A1.21 V (0.53%)228.8 V2.0 V (0.87%)36.4 W✓ OK (≤3%)
240 mm²415 A324 A0.94 V (0.41%)229.1 V1.54 V (0.67%)28.1 W✓ OK (≤3%)
300 mm²477 A372 A0.75 V (0.33%)229.3 V1.24 V (0.54%)22.5 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.24%)229.4 V0.93 V (0.4%)16.9 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 30A at 175 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 30A over 175m at 230V (voltage drop: 6.42V or 2.79%).

What is the power capacity of 30A at 230V?

At unity power factor, 30A at 230V supports 6.9 kW with a standard 30A circuit breaker.